TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
42
Troubleshooting
Controller Info Model Name TEC3x1x-xx
Software Version x.x.x.xxxx
Unit Name TECxxxxx
Device Name User-Supplied
Device Description TEC3000
Commissioning Supply Air Temperature Display Current
Temperature
Heat Command 0% 0 to 100%
Cool Command 0% 0 to 100%
Supply Fan No Yes or No
Aux No Yes or No
Update View Version x.x.x.xxxx Current Release of Software
Load Firmware
File list from USB drive
Restore*
File list from USB drive or local storage
*Configuration can be backed up to the
USB drive and restored to similar
models to expedite the commissioning
process.
Backup*
File list from USB drive or local storage
*Configuration can be backed up to the
USB drive and restored to similar
models to expedite the commissioning
process.
1. If the value is outside min/max limits, it is reassigned to the midpoint between min and max.
Table 11: Fault List (Part 1 of 3)
Faults Probable Causes Solutions
Remote Zone Temp Fail The External Zone Temperature sensor
has been disconnected or has failed.
1. Check the wiring of the sensor.
2. If intentionally disconnected, reset sensors
through the menu.
3. If the problem persists, order replacement
units and return the affected devices to
Johnson Controls under the RMA program.
Supply Temp Fail The External Supply Temperature
sensor has been disconnected or has
failed.
1. Check the wiring of the sensor.
2. If intentionally disconnected, result fault by
entering the menu, enter Control Setup, and
select Inputs to reset the sensors.
3. If the problem persists, order replacement
units and return the affected devices to
Johnson Controls under the RMA program.
Internal Sensor Fail An internal sensor has failed on the
TEC.
Order replacement units and return the affected
devices to Johnson Controls under the RMA
program.
Table 10: Menus and Submenus (Part 9 of 9)
Level 1 Level 2
(LCD Screen Name)
Level 3
(Default Values)
Available Values
1

Other manuals for Johnson Controls TEC3000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls TEC3000 Series and is the answer not in the manual?

Johnson Controls TEC3000 Series Specifications

General IconGeneral
BrandJohnson Controls
ModelTEC3000 Series
CategoryThermostat
LanguageEnglish

Related product manuals