TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
35
Schedule Schedule Options
Set Schedule
— See Scheduling
Optimal Start Enable No Yes or No
Temp Occ Duration 120 minutes 0 to 300 minutes
Motion Sensor Timeout 15 minutes 0 to 240 minutes
0 = PIR sensor disabled
Manual Occupancy Mode No Override No Override, Occupied, Unoccupied
Schedule Source Schedule Schedule or External
Display Settings Passcode Enable No Yes or No
Passcode* NA 0000 to 9999
*Passcode Enable = Yes
Brightness Setting 8 0 to 10 (most dim to brightest)
Enable Backlight Timeout Yes Yes or No
Units IP IP or SI
Time N/A
Time Zone Central All World Time Zones
Set Time Format 24 hour 24 hour or 12 hour
Date N/A
Set Date Format YYYY-MM-DD YYYY-MM-DD, or Day, Month DD, YYYY,
or MM-DD-YYYY
Language English English, French, Spanish
Show Fan Icon Yes Yes or No
Show Temp Yes Yes or No
Show Humidity Yes Yes or No
Show Off Icon Yes Yes or No
Show Hold Icon Yes Yes or No
Show Setpoint Yes Yes or No
Show Alarms Yes Yes or No
Show Occ Status Yes Yes or No
Show Unit Status Yes Yes or No
Show Date/Time Yes Yes or No
Control Setup General
Control Mode Auto Auto, Cooling, or Heating
Unit Enable Enable Enable or Shutdown
Fan Mode* Smart On, Auto, and Smart for single- and
variable-speed fans. Low, Medium, High,
Auto, and Smart for multi-speed units.
* Fan coil units only
Max Setpoint Offset 3 0 to 20 degrees (°F or °C based on Units
setting under Display Settings menu)
Fan On Delay* 30 seconds 0 to 120 seconds
* Fan coil units only
Table 10: Menus and Submenus (Part 2 of 9)
Level 1 Level 2
(LCD Screen Name)
Level 3
(Default Values)
Available Values
1