TEC3000 Series Networked and Wireless Proportional Fan Coil and Individual Zone Thermostat Controllers with
Dehumidification Capability Quick Start Guide
28
Cooling Ineffective The Supply Air Temperature has not
decreased below the configured Supply
Air Temperature Alarm Offset while
cooling has been active for at least the
Supply Air Temperature Alarm Delay.
Verify that the cooling elements on the rooftop are
functioning properly.
Supply Fan Fault The Supply Fan Status configured for
either BI1 or BI2 has not proved within
the configured Fan Alarm Delay.
1. Verify that the Supply Fan is operating when
turned on.
2. Verify that the Supply Fan Status wiring is
connected correctly.
Zone Temperature Too Cold The Zone Temperature has decreased
below the configured Zone Temp Low
Limit.
Verify that the TEC and the RTU heating are
enabled and functioning.
Zone Temperature Too Hot The Zone Temperature has increased
above the configured Zone Temp High
Limit.
Verify that the TEC and the RTU cooling are
enabled and functioning.
Table 8: Troubleshooting details
1
(Part 1 of 3)
Symptom Probable causes Solutions
The controller displays Idle with a
Unit Status of Cooling
Unavailable due to Changeover
despite being above cooling
setpoint, or with a status of
Heating Unavailable due to
Changeover despite being below
the setpoint.
The two-pipe fan coil/VAV system
does not have a changeover
sensor and switch connected, or
the sensor/switch has failed.
1. Check the wiring of the supply temperature
sensor/switch.
2. Verify that the changeover is set up correctly
for the type of sensor attached (sensor or
switch).
The changeover temperature is
sensing a hot supply, but the
controller is requesting cooling.
1. Verify that the supply is not in heating mode. If
it is, nothing can be done from the TEC.
2. Check the wiring of the supply temperature
sensor or switch.
3. Check the placement of the supply
temperature sensor or switch.
4. Verify that the changeover is set up correctly
for the type of sensor attached (sensor or
switch).
Changeover temperature is
sensing a cold supply, but the
controller is requesting heating.
1. Verify that the supply is not in cooling mode. If
it is, nothing can be done from the TEC.
2. Check the wiring of the supply temperature
sensor or switch.
3. Check the placement of supply temperature
sensor or switch.
4. Verify that the changeover is set up correctly
for the type of sensor attached (sensor or
switch).
The controller displays Idle with a
Unit Status of Cooling
Unavailable due to Control Mode
despite being above cooling
setpoint, or with a status of
Heating Unavailable due to
Control Mode despite being below
the setpoint.
The Control Mode is set to
Cooling Mode, but the controller
is requesting heating.
Change the Control Mode to Auto or Heating.
The Control Mode is set to
Heating Mode, but the controller
is requesting cooling.
Change the Control Mode to Auto or Cooling.
The controller provides an error
when trying to upgrade firmware.
The firmware on the USB drive is
below the minimum required
version.
Error code 1025.
Please use firmware version 3.0.2.xxxx (for
networked models) or 2.0.2.xxxx (for wireless
models) or higher.
A reboot is required to clear the Firmware
Mismatch fault that occurs.
Table 7: Fault list (Part 3 of 3)
Faults Probable causes Solutions