2.10.4 Paralleling Metering Submenu
Note:
The paralleling metering is only valid if the Decision-Maker
®
3500 controller is controlling a motor-operated circuit
breaker.
Connected to Bus displays if the generator is connected to the paralleling bus (the output breaker or contactor is
closed).
Avg Bus Voltage L-L displays the average of the three-phase line-to-line voltage measured by the paralleling bus
sensing.
Avg Gen Voltage L-L displays the average of the three-phase line-to-line voltage of the generator output.
Bus Frequency displays the cycle frequency of the paralleling bus.
Gen Frequency displays the cycle frequency of the generator.
Bus Total Power displays the real power provided by all the generators in the paralleling system.
Bus % of Rated kW displays the ratio between the Bus Total Power and the Bus Total Capacity (found in the
Generator Management screen) expressed as a percentage.
Bus % of Rated kVAR displays the ratio between the reactive load on all generators in the paralleling system and
the bus reactive capacity (the sum of 3/4 of the rated kW of all connected generators) expressed as a percentage.
2.11 Generator Information Menu
2.11.1 Generator Information Submenu
Total Run Time displays the total run time hours.
Hours Loaded displays the total loaded hours.
Hours Unloaded displays the total unloaded hours.
kW Hours displays the total kW hours.
Operating Hours displays the total operating hours.
Total Number of Starts displays the total number of times that the engine was started via the generator set controller.
Last Maintenance displays the date on the controller system clock when the last maintenance was performed.
Operating Hours Since Maintenance displays the total number of hours of operation since the last maintenance date.
Starts Since Maintenance displays the total number of generator set startup events since the last maintenance date.
Engine Hours Since Maintenance displays the total engine hours since last maintenance.
Loaded Since Maintenance displays the total loaded hour since last maintenance.
Unloaded Since Maintenance displays the unloaded hours since last maintenance.
kW Hours Since Maintenance displays the total kW hours since last maintenance.
Reset Maintenance Records: displays a Yes/No choice for the user to select.
Last Start displays the date when the generator set last operated.
Last Run Length displays the length of time that the engine ran the last time it was started via the generator set
controller.
Controller Serial No. displays the controller serial number.
Software Version displays the software version number. Use the version number to determine if an upgrade is needed
and/or when troubleshooting the controller.
ECM Serial No. displays the ECM serial number.
Genset Model No. displays the generator set model number. Only adjustable from SiteTech.

Table of Contents

Other manuals for Kohler 16EKOZD

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kohler 16EKOZD and is the answer not in the manual?

Kohler 16EKOZD Specifications

General IconGeneral
BrandKohler
Model16EKOZD
CategoryPortable Generator
LanguageEnglish

Related product manuals