TP-7045 3/18c10 Section 1 Introduction
Note: See text for complete explanation of installation
requirements.
Note: Use two hose clamps on each end of all flexible
exhaust hose connections.
1.2 Decision-Makerr 3500
Controller Information
The following data must be resident for the controller to
function.
D Application program contains the software that
controls system operation. The application file was
preprogrammed in the original controller at the
factory.
D Personality profile is specific to the engine and
alternator and was preprogrammed in the original
controller at the factory.
A backup disk of the personality p rofile
and
application program
is supplied with the literature
packet shipped with the generator set. Typically, the
Kohler authorized distributor/dealer passes this disk
onto the owner. Inform the owner to store this disk for
possible future use such as controller replacement or
other circumstances requiring a backup.
Note: If the personality d isk is NOT available, request
a replacement from Kohler Co. using the
generator set serial number or order number.
D User parameters unique to an installation include
timer values, setpoints, generator set data such as
voltage and input/output selections. These
parameters are typically set up for or by the installer at
the time of installation. User parameters are typically
recorded on the personality profile disk, a separate
backup disk/drive, or written on a paper form.
Note: If the user parameters are included on the
personality disk, the disk label should indicate
Site Program—Yes.
Note: After the unit is set up on the vessel, Kohler
authorized distributor/dealer saves any user
parameter changes to an external medium.
The installer or a Kohler authorized
distributor/dealer passes this information onto
the owner. Inform the owner to store this
information for possible future use such as
controller replacement or other circumstances
requiring a backup.
Note: Controller service replacement kits do not
include the three files. The service technician
must install the three files into the replacement
controller.