EasyManuals Logo
Home>Kohler>Portable Generator>Decision-Maker 3+

Kohler Decision-Maker 3+ User Manual

Kohler Decision-Maker 3+
224 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #141 background imageLoading...
Page #141 background image
141Section 8 Component Testing and AdjustmentTP-6356 4/12
8.17 Remote Serial Annunciator
(RSA II)
Adapted from Instruction TT-1485 1/11f.
The following information summarizes the setup items
when troubleshooting the remote serial annunciator
(RSA). Refer to the RSA installation instructions for
operation and function. See Figure 8-31 and
Figure 8-32 for RSA front panel illustration. See Section
8.19, Communication Module and Gauge Driver Circuit
Board.
8.17.1 RSA II Features and Connectors
All RSA II annunciators are factory set as the master
device, but can be changed to a slave device using a PC
and SiteTecht software that connects to the RSA II
front panel via a universal serial bus (USB) connection.
See Figure 8-33 for the circuit board connectors.
The RSA 1000 can be connected with the RSA II
provided that the master remote annunciator is an
RSA II.
The RSA annunciates faults using LEDs and an alarm
horn. Press the Alarm Silence/Lamp Test switch to test
the RSA indicator LEDs and horn. If the horn is activated
by a fault condition, press the Alarm Silence/Lamp Test
switch to quiet the alarm during servicing. The horn will
reactivate upon additional tests.
/Aux.
Figure 8-31 Remote Serial Annunciator (RSA II)
Figure 8-32 RSA II with ATS Controls

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kohler Decision-Maker 3+ and is the answer not in the manual?

Kohler Decision-Maker 3+ Specifications

General IconGeneral
BrandKohler
ModelDecision-Maker 3+
CategoryPortable Generator
LanguageEnglish

Related product manuals