81Section 5 Decision-Makerr 550 ControllerTP-6356 4/12
b. Create a new user parameter data backup disk
if any changes are made. See the Monitor II
software manual.
c. Disconnect the PC null modem RS-232 cable.
d. Install the P18 (RS-232) remote communication
connection, as necessary.
e. Swing the front controller panel up and replace
and tighten the screws, as necessary.
f. Replace the controller cover and hardware.
Tighten all controller screws.
23. Restore the generator set to service.
a. Perform the Menu 13, Communication, entries.
D Press the RESET MENU key on controller
keypad.
D Use the controller keypad to go to Menu 13,
Communications.
D With the information previously recorded
from step d., complete the communication
entries as necessary for the application. Use
the information from the controller operation
manual as necessary.
b. Perform the Menu 14, Programming Mode
entries.
D Press the RESET MENU key on controller
keypad.
D Use the controller keypad to go to Menu 14,
Programming Mode.
D Change the entries for the application as
necessary.
c. The generator set system is now ready to
function.
d. Move the generator set master switch to AUTO
for startup by remote transfer switch or remote
start/stop switch.