TT-1625 7/17 33
Selection Description
Display or Default
Selection
Setting Range Lamp
Alarm
Horn
User-Defined
Settings
Identity
Vendor Kohler Company Not adjustable
Product RSA III Not adjustable
Firmware Version 1.0.9 Not adjustable
Modbus
Modbus Baud Rate (kbps) 19.2 9.6, 19.2, 38.4, or 57.6
Is Modbus Master? True True or False
Modbus Slave Address 246 1--247
Modbus Timeout Factor (1--fast, 10 slow) 5 1--10
Received Modbus Message Count # Not adjustable
Modbus Error Count # Not adjustable
Product Connections
Connected GenSet Product none See Controller List *
Connected GenSet Address 1 1--247
Connected GenSet Timeout
45 seconds w
1--120 seconds
Connected ATS Product none
See ATS List [
Connected ATS Address 2 1--247
Connected ATS Timeout
45 seconds w
1--120 seconds
Connected (Slave) Annunciator 1 Product none
See Annunciator List ]
Connected (Slave) Annunciator 1 Address 3 (If RSA 1000, then 247) 1--247
Connected (Slave) Annunciator 1 Timeout
45 seconds w
1--120 seconds
Connected (Slave) Annunciator 2 Product none
See Annunciator List ]
Connected (Slave) Annunciator 2 Address 4 (If RSA 1000, then 247) 1--247
Connected (Slave) Annunciator 2 Timeout
45 seconds w
1--120 seconds
Connected (Slave) Annunciator 3 Product none
See Annunciator List ]
Connected (Slave) Annunciator 3 Address 5 (If RSA 1000, then 247) 1--247
Connected (Slave) Annunciator 3 Timeout
45 seconds w
1--120 seconds
Connected (Slave) Annunciator 4 Product none
See Annunciator List ]
Connected (Slave) Annunciator 4 Address 6 (If RSA 1000, then 247) 1--247
Connected (Slave) Annunciator 4 Timeout
45 seconds w
1--120 seconds
Connected (Slave) Annunciator 5 Product none
See Annunciator List ]
Connected (Slave) Annunciator 5 Address 7 (If RSA 1000, then 247) 1--247
Connected (Slave) Annunciator 5 Timeout
45 seconds w
1--120 seconds
Product Connections Inputs
EPS Supplying Load Indicator Generator
Local (hardwired),
Generator, or ATS
Digital Input 1 Source Local
Local (hardwired),
Generator, or ATS
Digital Input 1 Event Level Warning Warning or Fault
Warning--Yellow,
Fault--Red
Yes (if
Fault)
Digital Input 2 Source Local
Local (hardwired),
Generator, or ATS
Digital Input 2 Event Level Warning Warning or Fault
Warning--Yellow,
Fault--Red
Yes (if
Fault)
Digital Input 3 Source Local
Local (hardwired),
Generator, or ATS
Digital Input 3 Event Level Warning Warning or Fault
Warning--Yellow,
Fault--Red
Yes (if
Fault
Digital Input 4 Source Local
Local (hardwired),
Generator, or ATS
Digital Input 4 Event Level Warning Warning or Fault
Warning--Yellow,
Fault--Red
Yes (if
Fault
Digital Input 5 Source Local
Local (hardwired),
Generator, or ATS
Digital Input 5 Event Level Warning Warning or Fault
Warning--Yellow,
Fault--Red
Yes (if
Fault
* Controller List includes: Decision-Makerr 3+, 550, 3000, 3500, 6000, 8000, APM802, or KPC 1000.
[ ATS List includes: None, MPACr 750, MPACr 1000, MPACr 1200, or MPACr 1500.
] Annunciator List includes: None, RSA 1000, RSA II, or RSA III.
w The SiteTecht software may have a different default setting for selected devices.
Figure 55 User-Defined Settings

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kohler Decision-Makerr MPAC 1000 and is the answer not in the manual?

Kohler Decision-Makerr MPAC 1000 Specifications

General IconGeneral
BrandKohler
ModelDecision-Makerr MPAC 1000
CategoryController
LanguageEnglish

Related product manuals