4. Adjust - Used to select the indoor blower CFM
adjustment value by placing the jumper in appropriate
position.
If NORM is selected, indoor blower runs at normal
speeds.
If + is selected, indoor blower runs at approximately
10% higher speed than NORM setting.
If is selected, indoor blower runs at approximately
10% lower speed than NORM setting.
If the jumper is missing, the air handler control will
activate the Conguration Jumper is Missing alarm
and will automatically use the default factory setting.
Actual CFM values for different air handler sizes are
shown in Targeted CFM Tables.
Delay – Indoor blower cooling prole, delay for cool-
ing and heat pump operations.
When operating a heat pump, delay proles 1 and 2
are only applicable.
When operating a heat pump, and proles 3 and 4
are selected, the air handler control will default to
prole 1.
If the jumper is missing, the air handler control will activate
the Conguration Jumper is Missing alarm and will auto-
matically use the default factory setting.
delAy proFile 1
A - When cool or heat demand is initiated, motor ramps
up to 100% and runs at 100% until demand is
satised.
B - Once demand is met, motor ramps down to stop.
A
B
OFFOFF
100%
CFM
COMPRESSOR
DEMAND
delAy proFile 2
Cooling – Air Conditioner and Heat Pump:
A
BC
OFF
F
OFF
100% CFM
100% CFM
45 SEC.
COMPRESSOR
DEMAND
A - When cool demand is initiated, motor ramps up to
100% and runs at 100% until demand is satised.
B - Once demand is met, motor runs at 100% for 45
seconds.
C - C Motor ramps down to stop.
Heating – Heat Pump only:
OFF
OFF
100% CFM
100% CFM
HEATING DEMAND
45 SEC.
30 sec
delay
AB
C
D
A - When heat demand is initiated, 30 seconds motor-on
delay starts
B - After the motor-on delay expires, motor ramps up to
100% and runs at 100% until demand is satised.
C - Once demand is met, motor runs at 100% for 45
seconds.
D - Motor ramps down to stop.
delAy proFile 3
OF
F
OFF
82%CFM
100% CFM
COOLING DEMAND
7 1/2 MIN
A
B
C
A - When cool demand is initiated, motor ramps up to
82%
B - Motor runs at 82% for approximately 7.5 minutes
and then ramps up to 100% (unless the demand has
been satised) and motor runs at 100% until demand
is satised.
C - Once demand is met, motor ramps down to stop
delAy proFile 4
1/2 MIN
50% CFM
COOLING DEMAND
7 1/2 MIN
82% CFM
100%
CFM
1/2 MIN
50% CFM
B
A
D
E
A - When cool demand is initiated, motor ramps up to
50%
B - Motor runs at 50% for 30 seconds and ramps up to
82%
C - Motor runs at 82% for approximately 7.5 minutes
and then ramps up to 100% (unless the demand has
been satised) and motor runs at 100% until demand
is satised.
D - Once demand is met, motor runs at 50% for 30
seconds.
E - Motor ramps down to stop
seven-segment displAy
An on-board single character display (see gure 2 for dis-
play location) indicates general system status information
such as mode of operation, indoor blower CFM and error
codes. Multi-character strings are displayed with character
ON for one second, OFF for 0.5 seconds and one second
pause between the character groups.