CBX32MV-068 BLOWER PERFORMANCE
0 through 0.80 in. w.g. External Static Pressure Range
“ADJUST”
Jumper
Setting
Jumper Speed Positions
“HEAT” Speed “COOL” Speed
1 2 3 4 1 2 3 4
cfm cfm cfm cfm cfm cfm cfm cfm
+ 1875 1975 2090 2150 1640 1840 2075 2150
NORM 1760 1825 1920 2030 1465 1625 1800 2000
1550 1650 1725 1800 1250 1390 1560 1720
NOTES - The effect of static pressure, lter and electric heater resistance is included in the air volumes listed.
First stage cooling air volume is 70% of COOL speed setting. Continuous fan speed is approximately 28%, 38%, 70% and 100% (Jumper selectable) of the
same second-stage COOL speed selected, minimum 450 cfm.
Lennox iHarmony
®
Zoning System applications - minimum blower speed is 450 cfm.
CBX40UHV-024 BLOWER PERFORMANCE
0 through 0.80 in. w.g. External Static Pressure Range
“ADJUST”
Jumper
Setting
Jumper Speed Positions
“HEAT” Speed “COOL” Speed
1 2 3 4 1 2 3 4
cfm cfm cfm cfm cfm cfm cfm cfm
+ 715 855 1000 1130 465 690 900 1050
NORM 670 770 900 1035 425 620 825 950
580 700 800 930 385 560 735 850
NOTES - The effect of static pressure, lter and electric heater resistance is included in the air volumes listed.
First stage cooling air volume is 70% of COOL speed setting. Continuous fan speed is approximately 28%, 38%, 70% and 100% (Jumper selectable) of the
same second-stage COOL speed selected, minimum 250 cfm.
Lennox iHarmony
®
Zoning System applications - minimum blower speed is 250 cfm.
CBX40UHV-030 BLOWER PERFORMANCE
0 through 0.80 in. w.g. External Static Pressure Range
“ADJUST”
Jumper
Setting
Jumper Speed Positions
“HEAT” Speed “COOL” Speed
1 2 3 4 1 2 3 4
cfm cfm cfm cfm cfm cfm cfm cfm
+ 800 935 1070 1210 660 880 1100 1320
NORM 725 850 975 1100 600 800 1000 1200
655 765 880 990 540 720 900 1080
NOTES - The effect of static pressure, lter and electric heater resistance is included in the air volumes listed.
First stage cooling air volume is 70% of COOL speed setting. Continuous fan speed is approximately 28%, 38%, 70% and 100% (Jumper selectable) of the
same second-stage COOL speed selected, minimum 250 cfm.
Lennox iHarmony
®
Zoning System applications - minimum blower speed is 250 cfm.