Page 5
RIGHT-HAND DISCHARGE
1 - Determine which plugs are required for drain line
connections.
2 - With access door removed, remove drain line plugs
to install drain lines.
3 - Set unit so that it is sloped toward the upow drain
pan end of the unit and level from front to back of
unit (see gure 7).
4 - The horizontal conguration is shown in gure 2.
Drains
AIR FLOW
PLUGS
RIGHTHAND DRAINS
FIGURE 2. Right-Hand Discharge Conguration
5 - If the unit is suspended, the entire length of the
cabinet must be supported. If you use a chain or
strap, use a piece of angle iron or sheet metal
attached to the unit (either above or below) to
support the length of the cabinet. Use securing
screws no longer than 1/2 inch to avoid damaging
the coil or lter. See gure 3. Use sheet metal
screws to connect the return and supply air plenums
as required.
FRONT WEIV DNEWEIV
ANGLE IRON OR SHEET
METAL
E
ANCE 4 IN. (102 MM)
MAXIMUM 1/2"
LONG SCREW
AIR FLOW
FIGURE 3. Suspending Horizontal Unit
LEFT-HAND AIR DISCHARGE
For horizontal left-hand air discharge, the following eld
modications are required.
1 - Remove access panels and the horizontal drip
shield (-060 model) and the corrugated padding
between the blower and coil assembly. Discard the
corrugated padding.
2 - Pull the coil assembly from unit. Pull off the
horizontal drain pan.
3 - Remove the drain plugs from back drain holes on
horizontal drain pan and reinstall them on front holes.
IMPORTANT
After removal of drain pan plug(s), check drain hole(s)
to verify that drain opening is fully open and free of any
debris. Also check to make sure that no debris has fallen
into the drain pan during installation that may plug up the
drain opening.
4 - Rotate drain pan 180º front-to-back and install it on
the opposite side of the coil.
5 - Remove screws from top cap. Remove horizontal
drip shield screw located in the center of the back
coil end seal as illustrated in gure 4.
6 - Rotate horizontal drip shield 180º front-to-back.
7 - Remove plastic plug from left hole on coil front
end seal and reinstall plug in back hole. Reinstall
horizontal drip shield screw in front coil end seal.
Drip shield should drain downward into horizontal
drain pan inside coil.
90º
BEND
CABINET
SUPPORT
COIL SHOWN IN UPLOAD POSITION FOR EASY CONVERSION
TOP CAP SCREWS
DRAIN PAN
RE
INSTALLED
HERE
DRIP
SHIELD
DRAIN PAN
SHIPPING
LOCATION
TOP CAP ROTATED TO
CORRECT POSITION
———— DRAIN PLUGS ————
REINSTALLED HERE REMOVED FROM HERE
BACK COIL END SEAL
TOP
CAP
90º
BEND
ALIGN HOLES WITH
HOLES IN COIL END
PLATE. STARTING WITH
THE ROUND HOLES ON
THIS END.
FIGURE 4. Field Modication for
Left-Hand Discharge
8 - Rotate top cap 180º front-to-back and align with
unused screw holes. Holes must align with front
and back coil end plates. The top cap has a 45º
bend on one side and a 90º bend on the other.
The 90º bend must be on the same side as the
horizontal drain pan as illustrated in gure 4.