Page 30
IX-OPTIONAL ECH16 ELECTRIC HEAT
CHA16823 MODELS (TABLE 4)
Electric Heat
Model No.
& Net Weight
No.
of
Steps
Volts
Input
kw
Input
Btuh
Output
*Total Unit &
Electric Heat
Minimum Circuit
Ampacity
208 7.5 25,600 36.0
220 8.4 28,700
ECH1682/951
0
1
230 9.2 31,400
39.0
208/230v
(61H68)
240 10.0 34,100
460v
(61H73)
440 8.4 28,700
(38 lbs.)
1
460 9.2 31,400
20.0
480 10.0 34,100
208 11.3 38,600 49.0
220 12.6 43,000
ECH1682/951
5
1
230 13.5 46,100
54.0
208/230v
(61H69)
240 15.0 51,200
460v
(61H74)
440 12.6 43,000
(38 lbs.)
1
460 13.8 46,100
27.0
480 15.0 51,200
208 15.0 51,200 62.0
220 16.8 57,300
ECH1682/952
0
**2
230 18.4 62,800
69.0
208/230v
(61H70)
240 20.0 68,300
460v
(61H75)
440 16.8 57,300
(42 lbs.)
1
460 18.4 62,800
35.0
480 20.0 68,300
208 22.5 76,800 88.0
220 25.2 86,000
ECH1682/953
0
**2
230 27.5 93,900
99.0
208/230v
(61H71)
240 30.0 102,400
460v
(61H76)
440 25.2 86,000
(42 lbs.)
1
460 27.6 93,900
50.0
480 30.0 102,400
208 30.0 102,400 114.0
220 33.6 114,700
ECH1682/954
0
**3
230 36.8 125,600
129.0
208/230v
(61H72)
240 40.0 136,500
460v
(61H77)
440 33.6 114,700
(53 lbs.)
**2
460 36.8 125,600
65.0
480 40.0 136,500
*Refer to National Electrical Code manual to determine wire, fuse and disconnect size
requirements. Use wires suitable for at least 167°F.
**May be used with two stage control.
NOTE Fuse block must be ordered extra. Factory installed heaters will have the
fuse block factory installed. Fuse block must be installed in field installed
heaters. See Optional Accessories tables.
CHA16953 MODELS (TABLE 5)
Electric Heat
Model No.
& Net Weight
No.
of
Steps
Volts
Input
kw
Input
Btuh
Output
*Total Unit &
Electric Heat
Minimum Circuit
Ampacity
208 7.5 25,600 44.0
220 8.4 28,700
ECH1682/951
0
1
230 9.2 31,400
44.0
208/230v
(61H68)
240 10.0 34,100
460v
(61H73)
440 8.4 28,700
(38 lbs.)
1
460 9.2 31,400
23.0
480 10.0 34,100
208 11.3 38,600 49.0
220 12.6 43,000
ECH1682/951
5
1
230 13.5 46,100
54.0
208/230v
(61H69)
240 15.0 51,200
460v
(61H74)
440 12.6 43,000
(38 lbs.)
1
460 13.8 46,100
27.0
480 15.0 51,200
208 15.0 51,200 62.0
220 16.8 57,300
ECH1682/952
0
**2
230 18.4 62,800
69.0
208/230v
(61H70)
240 20.0 68,300
460v
(61H75)
440 16.8 57,300
(42 lbs.)
1
460 18.4 62,800
35.0
480 20.0 68,300
208 22.5 76,800 88.0
220 25.2 86,000
ECH1682/953
0
**2
230 27.5 93,900
99.0
208/230v
(61H71)
240 30.0 102,400
460v
(61H76)
440 25.2 86,000
(42 lbs.)
1
460 27.6 93,900
50.0
480 30.0 102,400
208 30.0 102,400 114.0
220 33.6 114,700
ECH1682/954
0
**3
230 36.8 125,600
129.0
208/230v
(61H72)
240 40.0 136,500
460v
(61H77)
440 33.6 114,700
(53 lbs.)
**2
460 36.8 125,600
65.0
480 40.0 136,500
*Refer to National Electrical Code manual to determine wire, fuse and disconnect size
requirements. Use wires suitable for at least 167°F.
**May be used with two stage control.
NOTE Fuse block must be ordered extra. Factory installed heaters will have the
fuse block factory installed. Fuse block must be installed in field installed
heaters. See Optional Accessories tables.