GENERAL TECHNICAL DATA
MAIN PARTS
LOAD-BEARING STRUCTURE
Galvanised (1 mm for mod. 10-50 and 1.5 mm for mod. 60-70) plate, insulated wherever it is in indirect contact with
the heat-carrying fluid. Condensate collecting tray in insulated, galvanised plate complete with fittings for condensate
drainage. Slots for easy wall-mounting and levelling of unit.
HEAT EXCHANGER COIL
Coils in copper piping expanded into aluminium fins in continuous block. Copper headers with brass connections
equipped with male fittings (gas thread) and easily accessible air valves.
Water fittings placed on the left (facing the unit). They may be supplied on the right on request.
ELECTRIC FAN UNIT
Double-inlet centrifugal fans with statically and dynamically balancing horizontally-oriented aluminium impellers.
Single-phase asynchronous electric motor with overload cutout. 3 speeds of rotation. The motor is directly coupled to
the fans and cushioned with flexible mountings to ensure low noise.
ACCESSORIES
SSP Section with external air intake (manual). Made in galvanised sheet metal, it allows a change of air in the
rooms. Internal air flow: 100%-66.6%. External air flow: 0%¸33.3%
SRE Heating section with electric heating element (380V), fabricated to international safety standards. It comes
complete with safety thermostat with automatic reset, interface control relay, wiring and control panel with on-
off/magnetothermal switch
FAM Connecting flange
GAM Vibration isolation joint
PAM Straight intake/delivery plenum
BAM Intake/delivery union with circular fittings
RAM 90° intake/delivery plenum
SFA Air filter section. Filtering membrane enclosed within a metal frame for easy extraction. Filtering rate EU3.
Regenerable by washing in water, blowing, suction
AUXILIARY COIL for heating (4 rows)
4 AND 6-ROW COIL
Fans - Motors
No.
Rows No.
Fittings (ØAF)
Ø
Rows No.
Fittings
(ØAC) Ø
Condensate drain fitting
(ØC) Ø mm
Height
mm
Width
mm
Depth
mm
(A)
mm
(
B)
mm
No. x Ø BAM mm
Net weight
kg
Electric fan power W
Electric fan current A
Standard coil
(H)
(L)
(P)
ELECTRICITY SUPPLY 230 V/1/50 Hz
MODELHH 10 HH 20 HH 30 HH 40 HH 50 HH 60 HH 70
1-1 2-1 2-1 2-1 2-1 1-1 2-2
333 3344
1/2" 1/2" 3/4" 3/4" 1" 1"1/4 1"1/2
111 1122
1/2" 1/2" 1/2" 1/2" 3/4" 1" 1"1/4
20 20 20 20 20 20 20
299 299 324 324 374 674 674
650 1.000 1.100 1.339 1.339 1.341 2.028
533 533 533 533 533 853 853
197 197 222 222 272 572 572
548 898 998 1.237 1.237 1.239 1.926
2xØ200 3xØ200 3xØ200 4xØ200 4xØ200 2xØ200 4xØ200
28 26 41 46 57 117 192
162 218 322 340 582 1.320 2.600
0,72 0,97 1,43 1,51 2,58 5,86 11,54
Auxiliary coil
Tab. 2
INSTALLATION - OPERATING & MAINTENANCE MANUAL
Page 5

Other manuals for Lennox COMFAIR HH Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox COMFAIR HH Series and is the answer not in the manual?

Lennox COMFAIR HH Series Specifications

General IconGeneral
BrandLennox
ModelCOMFAIR HH Series
CategoryFan
LanguageEnglish

Related product manuals