Page 14
12 - Install the side vent sealing plates and gaskets on
the exterior of the cabinet as shown in FIGURE
23. Secure with six mounting screws (four reused
and two provided from bag assembly). Holes are
pre-punched in the parts and cabinet, no drilling is
required.
13 - Install sheet metal screws (provided) to seal extra
two holes in cabinet not used with side vent clamps.
IMPORTANT
Side vent sealing plates and side vent sealing gaskets
must be used when converting to right side venting.
Failure to use gaskets and plates may lead to improper
operation of unit.
Top Vent Configuration
Exhaust/Air
Intake Connections
Pipe Clamp
Hose Clamp
FIGURE 20
Sheet Metal
Patch Plate
Patch Plate Top Cap
FIGURE 21
Crawl Space and Extended Horizontal Venting
Lennox provides kit 51W18 (USA) and kit 15Z70 (Cana-
da) to install 2” or 3” PVC exhaust piping through the oor
joists and into the the crawl space. See FIGURE 22.
This kit can also be used as a supplemental drain for in-
stallations with condensate run back in the vent pipe (ie.
long horizontal runs, unconditioned spaces, etc.).
Venting In A Crawl Space
Basement Floor
KIT 51W18
(USA)
KIT 15Z70
(CANADA)
FIGURE 22

Other manuals for Lennox EL296DFE Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox EL296DFE Series and is the answer not in the manual?

Lennox EL296DFE Series Specifications

General IconGeneral
BrandLennox
ModelEL296DFE Series
CategoryFurnace
LanguageEnglish

Related product manuals