Defrost System
This section addresses:
Emergency Heat
Defrost System Overview
Defrost Control Connections, Jumper Settings and Fea-
tures
Operational Mode Overview (Calibration, Normal and
Defrost)
Defrost Cycle Actuation
EMERGENCY HEAT (AMBER LIGHT)
An emergency heat function is designed into some room
thermostats. This feature is applicable when isolation of
the outdoor unit is required, or when auxiliary electric heat
is staged by outdoor thermostats. When the room thermo-
stat is placed in the emergency heat position, the outdoor
unit control circuit is isolated from power and eld-provid-
ed relays bypass the outdoor thermostats. An amber indi-
cating light simultaneously comes on to remind the home-
owner that he is operating in the emergency heat mode.
Emergency heat is usually used during an outdoor unit
shutdown, but it should also be used following a power
outage if power has been o󰀨 for over an hour and the out-
door temperature is below 50°F (10°C). System should be
left in the emergency heat mode at least six hours to allow
the crankcase heater su󰀩cient time to prevent compres-
sor slugging.
DEFROST SYSTEM OVERVIEW
The control monitors ambient temperature, outdoor coil
temperature, and total run time to determine when a de-
frost cycle is required. The coil temperature probe is de-
signed with a spring clip to allow mounting to the outside
coil tubing. The location of the coil sensor is important for
proper defrost operation.
NOTE The demand defrost control accurately measures
the performance of the system as frost accumulates on the
outdoor coil. This typically will translate into longer running
time between defrost cycles as more frost accumulates on
the outdoor coil before the demand defrost control initiates
defrost cycles.
DEFROST CONTROL CONNECTIONS, JUMPERS
SETTINGS AND FEATURES
Defrost Temperature Termination Jumper Settings (P1)
The demand defrost control selections are: 50, 70, 90 and
100°F (10, 21, 32 and 38°C). The shunt termination pin
is factory set at 50°F (10°C). If temperature shunt is not
installed, default termination temperature is 90°F (32°C).
Test Pins (P1) Function
Placing the jumper on the eld test pins (P1) allows the
technician to:
Clear short cycle lockout
Clear ve-strike fault lockout
Cycle the unit in and out of defrost mode
Place the unit in defrost mode to clear the coil
Compressor Delay Mode (P5)
The demand defrost control has a eld-selectable function
to reduce occasional sounds that may occur while the unit
is cycling in and out of the defrost mode. When a jumper
is installed on the DELAY pins, the compressor will be
cycled o󰀨 for 30 seconds going in and out of the defrost
mode. Units are shipped with jumper installed on DELAY
pins.
NOTE - The 30 second o cycle is NOT functional when
jumpering the TEST pins.

Other manuals for Lennox HFC-410A Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox HFC-410A Series and is the answer not in the manual?

Lennox HFC-410A Series Specifications

General IconGeneral
BrandLennox
ModelHFC-410A Series
CategoryHeat Pump
LanguageEnglish

Related product manuals