EasyManuals Logo
Home>Lennox>Heat Pump>HP29 Series

Lennox HP29 Series User Manual

Lennox HP29 Series
27 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #6 background imageLoading...
Page #6 background image
LATCH RELAY K6
14
568
9
10
12
13 14
FIGURE 5
SET
RESET
Page 6
I−UNIT COMPONENTS
The HP29−090 and HP29−120 components are shown in
figures 1 and 2.
A−CONTROL BOX COMPONENTS
The HP29−090 control box components are shown in fig
ure 3. The HP29−120P control box components are shown
in figure 4.
1 − Disconnect Switch S48
(Option −2 Units)
HP29 heat pumps units may be equipped with an optional
disconnect switch S48. S48 is a factory−installed toggle
switch used to disconnect power to the unit.
2 − Outdoor Fan Capacitors C1 (all units)
and C2 (120P)
All HP29 units use single−phase condenser fan motors.
Motors are equipped with a fan run capacitor to maximize
motor efficiency. Outdoor fan capacitors C1 and C2 assist
in the start up of condenser fan motors B4 and B5. Capaci
tor ratings are on outdoor fan motor nameplates.
3 − Compressor Contactor K1 (all units)
All compressor contactors are three−pole−double break
contactors with a 24V coil. K1 energizes compressor B1 in
both HP29−090 and HP29−120 units. The contactor is en
ergized from indoor thermostat terminal Y when thermo
stat demand is present.
4 − Low Ambient Thermostat S41
(HP29−120 only)
S41 is a N.C. limit which opens on temperature fall at 55+
5_F. The switch resets when temperature rises to 65+ 6_F.
S41 opens and de−energizes K68 which de−energizes out
door fan B5. When S41 closes, fans will be re−energi
zed.This intermittent fan operation increases indoor evap
orator coil temperature to prevent icing.
5 − Latch Relay K6 (all units)
HP29 units are plumbed so that the unit is in cooling mode
when the reversing valve is energized. Latch relay K6 con
trols operation of the reversing valve and is controlled (indi
rectly) by the indoor thermostat. The combined operation
of latch relay K6 and transfer relay K8 allows the HP29
heat pumps to use a conventional heat/cool thermo
stat instead of a heat pump thermostat.
A latch relay (figure 5 ) has two coils: a SET" coil and a
RESET" coil. When 24VAC is applied to the SET" coil, the
normally open contacts close and the normally closed con
tacts open. When power is removed from the SET" coil,
nothing happens; the NO. contacts remain closed and the
N.C. contacts remain open. The contacts do not return to
their normal position until the RESET" coil is energized.
Once the contacts are reset, they remain in their normal
position when power is removed.
HP29 units use a DPDT
latch relay. Each set of nor
mally open contacts con
trols a reversing valve.
When the SET" coil is en
ergized, the normally open
contacts close to energize
the reversing valve (there
by placing the unit in the
cooling mode). When pow
er is removed from the
SET" coil (such as when
thermostat demand is satis
fied), the normally open
contacts remain closed, the
reversing valve remains en
ergized and the unit re
mains in the cooling mode.
When a heating demand is initiated, the RESET" coil is
energized. The normally open contacts open and the re
versing valve is deenergized (thereby placing the unit in
the heating mode). When heat demand is satisfied and
power to the RESET" coil is removed, the normally open
contacts remain open, the normally closed contacts re
main closed and the unit remains in the heating mode.

Other manuals for Lennox HP29 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox HP29 Series and is the answer not in the manual?

Lennox HP29 Series Specifications

General IconGeneral
BrandLennox
ModelHP29 Series
CategoryHeat Pump
LanguageEnglish

Related product manuals