FIGURE 6
CONDENSER FAN
(NOT SHOWN)
TOP OF CABINET
CONTACTOR
THERMOME
TER
WELL
TERMINAL BOX
LIQUID LINE
SERVICE VALVE
AND GAUGE
PORT
SUCTION VALVE
AND GAUGE PORT
COMPRESSOR
LOW PRESSURE
SWITCH
HIGH PRESSURE
SWITCH
GROUND LUG
PARTS ARRANGEMENT FOR HS26 (LATE MODEL)
TIMED OFF CONTROL (TOC)
DUAL CAPACITOR
E−Compressor
Tables1 and 2 show the specifications for compressors
used in HS26 series units.
F−Compressor High Temperature Limit
(Early Models)
Each scroll compressor in the HS26−261, −311, −411, −461
is equipped with a compressor high temperature limit lo
cated on the outside top of the compressor. The sensor is a
SPST thermostat which opens when the discharge tem
perature exceeds 280_F + 8_F (138_C + 4.5_C) on a tem
perature rise. When the switch opens, the circuit to the
compressor contactor and the time delay is de−energized
and the unit shuts off. The switch automatically resets
when the compressor temperature drops below 130_F +
14_F. (54_C + 8_C)
The sensor can be accessed by prying off the snap plug on
top of the compressor (see figure 7). Make sure to securely
seal the limit after replacement. The limit pigtails are lo
cated inside the unit control box. Figure 8 shows the ar
rangement of compressor line voltage terminals and dis
charge sensor pigtails.
Table 1 (Early Models)
HS 26
Unit
Vac Phase LRA RLA Oil fl.oz.
−261 208/230 1 62.5 11.6 28*
−311 208/230 1 76.0 13.5 28*
−411 208/230 1 90.5 18.0 34*
−461 208/230 1 107 20.0 38*
*Shipped with conventional white oil (Sontex 200LT). 3GS oil may be
used if additional oil is required.
Table 2 (Late Models)
HS26
Unit
Vac Phase LRA RLA Oil fl. oz.
−018 208/230 1 47.0 8.4 38*
−024 208/230 1 56.0 10.3 30*
−030 208/230 1 72.5 13.5 30*
−036 208/230 1 88.0 16.0 42*
−042 208/230 1 104.0 18.0 42*
−048 208/230 1 129.0 23.7 53*
−060 208/230 1 169.0 28.8 50*
−036 208/230 3 88.8 10.3 42*
−042 208/230 3 77.0 12.5 42*
−048 208/230 3 99.0 13.5 53*
−048 460 3 49.5 7.4 53*
−060 208/230 3 123.0 17.4 53*
−060 460 3 62.0 9.0 53*
*Shipped with conventional white oil (Sontex 200LT). 3GS oil may be
used if additional oil is required.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox HS26-024 and is the answer not in the manual?

Lennox HS26-024 Specifications

General IconGeneral
BrandLennox
ModelHS26-024
CategoryAir Conditioner
LanguageEnglish

Related product manuals