EasyManuals Logo
Home>Lennox>Air Conditioner>HS26-024

Lennox HS26-024 User Manual

Lennox HS26-024
18 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #7 background imageLoading...
Page #7 background image
Page 7
FIGURE 7
COMPRESSOR HIGH TEMPERATURE LIMIT CHANGEOUT (EARLY MODELS ONLY)
Instructions
1 With power off, disconnect wiring to limit.
2 Dislodge limit/cap assembly from compressor. Plastic cap and silicone seal
will break away. Discard all pieces.
3 Remove thermostat and grommet from compressor. Thoroughly clean all
blue adhesive and white silicone thermal grease from compressor and the
inside of the thermostat tube. Thermostat tube should be clean and free of
debris.
4 Using Lennox kit 93G8601, dip end of thermostat into plastic bottle labeled
Silicone Thermal Grease G.E. #G641" and coat end of thermostat. Care
fully insert thermostat/grommet assembly into thermostat tube of compres
sor. Avoid contact with top of compressor.
5 Clean excess thermal grease from under cap lip and top lip of compressor
opening.
6 Install protector assembly as shown, feeding wire leads through channel
provided in cap.
7 Apply a bead of sealant around lip of cap at area shown in illustration and
into the thermostat tube area.
8 Install assembly as shown. Align wires to channel in compressor shell. Suf
ficient force is required to snap plastic cap into tube to engage all three
prongs.
9 Reconnect wiring.
10After completing thermostat replacement, discard remaining parts.
PLASTIC CAP
PRONG
GROMMET
SEALANT
(BLUE)
COMPRESSOR
THERMAL
GREASE
(WHITE)
LIMIT
(THERMOSTAT)
G−High/Low Pressure Switch
A manualreset singlepole singlethrow high pressure switch
located in the liquid line, shuts off the compressor when liquid
line pressure rises above the factory setting. The switch is nor
mally closed and is permanently adjusted to trip (open) at 410
+ 10 psi. See figure 5 or 6 for switch location
COMPRESSOR TERMINAL BOX
C
S
R
COMPRESSOR
TERMINALS
FIGURE 8
WARNING
COMPRESSOR MUST BE GROUNDED. DO
NOT OPERATE WITHOUT PROTECTIVE COV
ER OVER TERMINALS. DISCONNECT ALL
POWER BEFORE REMOVING PROTECTIVE
COVER. DISCHARGE CAPACITORS BEFORE
SERVICING UNIT. COMPRESSOR WIRING DIA
GRAM IS FURNISHED INSIDE COMPRESSOR
TERMINAL BOX COVER. FAILURE TO FOL
LOW THESE PRECAUTIONS COULD CAUSE
ELECTRICAL SHOCK RESULTING IN INJURY
OR DEATH.
DISCHARGE TEMPERATURE
SENSOR WIRES
TO CONTROL BOX
(TO COMP. TERM. BOX IN
461 UNITS)
EARLY MODELS ONLY
An autoreset singlepole singlethrow low pressure switch
located in the suction line shuts off the compressor when
suction pressure drops below the factory setting. The
switch is normally closed and is permanently adjusted to
trip (open) at 25 + 5 psi. The switch automatically resets
when suction line pressure rises above 55 + 5 psi. See fig
ure 5 or 6 for switch location.
H−Dual Capacitor
The compressor and fan in HS26 single−phase units use
permanent split capacitor motors. A single dual" capacitor
is used for both the fan motor and the compressor (see unit
wiring diagram). The fan side of the capacitor and the com
pressor side of the capacitor have different mfd ratings. The
capacitor is located inside the unit control box (see figure 5
or 6). Tables 3 and 4 show the ratings of the dual capacitor.
TABLE 3 (Early Models)
HS26 DUAL CAPACITOR RATING
UNITS
FAN
MFD
HERM MFD VAC
HS26−261 5 30 370
HS26−311 5 35 370
HS26−411,−461 5 35 440
TABLE 4 (Late Models)
HS26 DUAL CAPACITOR RATING
UNITS FAN MFD HERM MFD VAC
HS26−018 4 30 370
HS26−024,−030 5 40 370
HS26−036 5 50 370
HS26−042 5 55 370
HS26−048 7.5 60 370
HS26−060 10 80 370

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox HS26-024 and is the answer not in the manual?

Lennox HS26-024 Specifications

General IconGeneral
BrandLennox
ModelHS26-024
CategoryAir Conditioner
LanguageEnglish

Related product manuals