INNOV@ ECFAN DMR -AGU-0912-E • 23 •
12 Technical Data
Tab. 11 DX unit - air cooled - DMADR / DMAUR
MODELS:
V/Ph/Hz
400V / 3Ph + N + PE / 50Hz
m
3
/h
1785 2150 3530 3530 3700 5100 5100 5100
-
Scroll
Cooling capacity (24°C; 50% RH;
condensing temperature 45°C)
kW
6.0 8.0 9.9 11.0 13.0 17.2 19.9 22.0
Cooling capacity (24°C; 50% RH;
external air temperature 35°C)
kW
5.9 7.7 9.3 10.6 12.7 15.8 18.4 20.5
kW
1.5 1.9 2.3 2.6 3.2 4.2 4.9 5.5
A
2.8 3.6 4.4 5.1 6.2 8.0 8.7 10.5
A
5 6 6 7 10 13 13 15
A
24 32 40 46 50 66 74 101
l
1.00 1.00 1.10 1.10 1.36 1.65 1.65 1.65
m
2
0.27 0.27 0.45 0.45 0.45 0.53 0.53 0.53
-
25 x 21.65
Nr.
3 4 3 3 4 4 5 5
Type
Hydrophilic
mm
1.8
-
1.00 0.96 1.00 1.00 0.98 0.99 0.94 0.92
-
Radial - EC
V/Ph/Hz
400V / 3Ph / 50Hz
Nr.
1
A
0.24 0.33 0.51 0.51 0.47 1.05 1.19 1.19
W
151 203 315 315 291 652 743 743
Pa
30
Pa
557 505 477 477 453 174 144 144
-
G3
m
2
2.2 2.2 3.6 3.6 3.6 5.0 5.0 5.0
-
1
kW
1.6 3.2
Nr.
1 2
-
Aluminium
kW
5.1 5.5 9.0 9.0 9.1 10.3 10.3 10.3
m
2
0.22 0.37
Heating capacity (water 45/40°C)
kW
4.2 4.6 7.8 7.8 8.0 9.2 9.2 9.2
m
2
0.22 0.37
m
3
/h
0.730 0.792 1.365 1.365 1.393 1.595 1.595 1.595
kPa
8.2 9.4 15.5 15.5 16.1 20.3 20.3 20.3
kPa
3.3 3.9 4.4 4.4 4.6 6.0 6.0 6.0
dm
3
0.9 1.3
Max. theoretical capacity
kg/h
2.80 3.17 4.45 5.22 5.01 10.09 6.90 6.50
kg/h
3
kW
2.25
dB(A)
46 48 48 49 51 52 53 53
mm
1875 x 600 x 600 1875 x 900 x 600
kg
150 157 195 210 230 245 255 257
(**)
At 1,5 meters height, 2 meters frontal distance in free field; down flow units (30 Pa AESP); nominal air flow