Page 3
SPECIFICATIONS 3-4 TON
Model No. LCA/LGA036 LCA/LGA042 LCA/LGA048
Cooling Efficiency type Standard High Standard High Standard High
Gross Cooling Capacity — Btuh (kW) 38,000 (11.1) 38,000 (11.1) 44,200 (12.9) 44,500 (13.0) 50,500 (14.8) 50,200 (14.7)
¡Net Cooling Capacity — Btuh (kW) 36,000 (10.6) 35,800 (10.5) 42,000 (12.3) 42,500 (12.5) 48,000 (14.1) 48,000 (14.1)
Ratings
Total Unit Power (kW) 3.9 3.4 4.6 4.0 5.0 4.6
¡SEER (Btuh/Watt) 10.0 12.0 10.0 12.0 10.0 12.0
EER (Btuh/Watt) 9.2 10.5 9.1 10.6 9.6 10.4
©Sound Rating Number (db) 82
Refrigerant Charge Furnished (HCFC-22)
6 lbs. 10 oz.
(3.01 kg)
8 lbs. 6 oz.
(3.80 kg)
6 lbs. 10 oz.
(3.01 kg)
8 lbs. 13 oz.
(4.00 kg)
7 lbs. 9 oz.
(3.43 kg)
9 lbs. 8 oz.
(4.31 kg)
Model No. LGA036 LGA042 LGA048
Only
Heat Input Type Standard Standard Dual or High Standard Dual or High
Heating
Input (low) — Btuh (kW) - - - - - - - - 92,000 (27.0) - - - - 92,000 (27.0)
Capacity
Output (low) — Btuh (kW) - - - - - - - - 72,700 (21.3) - - - - 72,700 (21.3)
Input (High) — Btuh (kW) 78,000 (22.9) 78,000 (22.9) 125,000 (36.6) 78,000 (22.9) 125,000 (36.6)
Gas (at Sea
Output (High) — Btuh (kW) 61,600 (18.1) 61,600 (18.1) 98,750 (29.0) 61,600 (18.1) 98,750 (29.0)
Level)
A.G.A./C.G.A. Thermal Efficiency / AFUE 80.0% / 78.0%
Gas Supply Connections npt — in. - Natural or LPG/Propane 1/2
Natural 7 (1.7)
Pressure — wc. in. (kPa)
LPG/Propane 11 (2.7)
Blowerwheelnomi-
naldia.xwidth — in.(mm)
11-1/2 X 9 (292 X 229)
Nominal Motor output hp (W) .75 (560)
Motor
Voltage & phase 208/230v - 1ph or 3 ph or 460v, 575v-3ph
Nominal 1.5 (1.1)
hp(kW)
Max. usable 1.72 (1.3)
¢Motor &
Voltage & phase 208/230v - 1ph, 208/230v, 460v or 575v-3ph
Drives
(Drive kit #) RPM range (1) 615 - 920 or (2) 800-1105
and Drive
Nominal 2 (1.5)
Selection
hp (kW)
Max. usable 2.3 (1.7)
¢Motor &
Voltage & phase 208/230v, 460v or 575v-3ph
Drives
(Drive kit #) RPM range (3) 920 - 1230
Nominal 3 (2.2)
(2.2 kW)
hp (kW)
Max. usable 3.45 (2.6)
¢Motor &
Voltage & phase 208/230v, 460v or 575v-3ph
Drives
(Drive kit #) RPM range (4) 1070 - 1325
Net face area — sq. ft. (m
2
) 6.25 (0.58)
Tube diameter — in. (mm) & No. of rows 3/8 (9.5) - 2 3/8 (9.5) - 3 3/8 (9.5) - 2 3/8 (9.5) - 3
Evaporator
Fins per inch (m) 15 (591)
Coil
Drain connection no. & size - in. (mm)
fpt
(1) 3/4 (19)
Expansion device type Balanced Port Thermostatic Expansion Valve, removeable power head
Net face area — sq. ft. (m
2
) 14.6 (1.35)
Tube diameter — in. (mm) & No. of rows 3/8 (9.5) - 1.3 3/8 (9.5) - 2 3/8 (9.5) - 1.3 3/8 (9.5) - 2
Fins per inch (m) 20 (787)
Diameter — in. (mm) & No. of blades 24 (610) - 3
Total Air volume — cfm (L/s) 4000 (1890) 4200 (1980)
Motor horsepower (W) 1/3 (224)
Motor rpm 1075
Total Motor watts 320 360
Type of filter Disposable Commercial Grade Pleated
(furnished)
No. and size — in. (mm) (2) 16 x 25 x 2 (406 x 635 x 51)
Electrical characteristics
208/203v -— 60 hertz — 1 phase
208/230v, 460v or 575v — 60 hertz — 3 phase
¡Rated in accordance with ARI Standard 210/240 and certified to ARI; 95_F (35_C) outdoor air temperature and 80_F (27_C) db/67_F (19_C) wb entering evaporator air; mini-
mum external duct static pressure.
©Sound Rating Number rated in accordance with test conditions included in ARI Standard 270.
¢Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. Maximum usable output of motors
furnished by Lennox are shown. In Canada, nominal motor output is also maximum usable motor output. If motors of comparable output are used, be sure to keep within the
service factor limitations outlined on the motor nameplate.
NOTE — Net capacity includes evaporator blower motor heat deduction. Gross capacity does not include evaporator blower motor heat deduction.