SPECIFICATIONS 5-6 TON
Model No. LCA/LGA060 LCA/LGA072
Cooling Efficiency Type Standard High Standard High
Gross Cooling Capacity — Btuh (kW) 60,500 (17.7) 63,000 (18.5) 76,000 (22.3) 74,500 (21.8)
¡Net Cooling Capacity — Btuh (kW) 57,500 (16.9) 60,000 (17.6) 72,000 (21.1) 71,500 (21.0)
Ratings
Total Unit Power (kW) 6.5 5.8 7.6 6.85
¡SEER (Btuh/Watt) 10.0 12.0 - - - - - - - -
EER (Btuh/Watt) 8.8 10.3 9.0 10.5
©Sound Rating Number (db) 82
Refrigerant Charge Furnished (HCFC-22)
7 lbs. 14 oz.
(3.57 kg)
10 lbs. 0 oz.
(4.54 kg)
9 lbs. 5 oz.
(4.22 kg)
9 lbs. 13 oz.
(4.45 kg)
Model No. LGA060 LGA072
LGA Models
Heat Input Type Standard Dual or High Standard Dual or High
Two Stage
Input (low) — Btuh (kW) - - - - 92,000 (27.0) - - - - 92,000 (27.0)
Output (low) — Btuh (kW) - - - - 72,700 (21.3) - - - - 72,700 (21.3)
LPG/Propane
Input (High) — Btuh (kW) 78,000 (22.9) 125,000 (36.6) 78,000 (22.9) 125,000 (36.6)
Gas
Output (High) — Btuh (kW) 61,600 (18.1) 98,750 (28.9) 61,600 (18.1) 98,750 (28.9)
A.G.A./C.G.A. Thermal Efficiency / AFUE 80.0% / 78.0%
Gas Supply Connections npt — in. - Natural or LPG/Propane 1/2
Natural 7
Supply Pressure — wc. in. (kPa)
LPG/Propane 11
Blower wheel nominal dia. x width — in. (mm) 11-1/2 x 9 (292 x 229)
Nominal motor output — hp (kW) .75 (.56) - - - -
Motor
Voltage & phase 208/230v -1 or 3ph or 460, 575v-3ph - - - -
Nominal motor horsepower (kW) 1.5 (1.1)
1.5 hp (1.1 kW)
Max. usable motor output — hp (kW) 1.72 (1.3)
Voltage & phase 208/230v - 1ph, 208/230v, 460v or 575v-3ph
Evaporator
(Drive kit #) RPM range (1) 615 - 920 or (2) 800 - 1105
Blower
Nominal motor output — hp (kW) 2 (1.5)
Drive Selection
2 hp (1.5 kW)
Max. usable motor output — hp (kW) 2.3 (1.7)
Voltage & phase 208/230v, 460v or 575v-3ph
(Drive kit #) RPM range (3) 920 - 1230
Nominal motor horsepower (kW) 3 (2.2)
3 hp (2.2 kW)
Max. usable motor output — hp (kW) 3.45 (2.6)
Voltage & phase 208/230v, 460v or 575v-3ph
(Drive kit #) RPM range (4) 1070 -1325
Net face area — sq. ft. (m
2
) 6.25 (0.58)
Tube diameter — in. (mm) & No. of rows 3/8 (9.5) — 2 3/8 (9.5) — 3 3/8 (9.5) — 3 3/8 (9.5) — 4
Evaporator Coil
Fins per inch (m) 15 (591)
Drain connection no. & size — in. (mm) fpt (1) 3/4 (19)
Expansion device type Balanced Port Thermostatic Expansion Valve, removeable power head
Net face area — sq. ft. (m
2
) 14.6 (1.35)
Condenser Coil
Tube diameter — in. (mm) & No. of rows 3/8 (9.5) — 2
Fins per inch (m) 20 (788)
Diameter — in. (mm) & No. of blades 24 — 3
Total Air volume — cfm (L/s) 4200
Condenser
Motor horsepower (W) 1/3 (248)
Motor rpm 1075
Total Motor watts 360
Type of filter Disposable Commercial Grade Pleated
(furnished)
No. and size — in. (mm) (2) 16 x 25 x 2 (406 x 635 x 51)
Electrical characteristics
208/203v -— 60 hertz — 1 phase
208/230v, 460v or 575v
60 hertz — 3 phase
208/230v, 460v or 575v
60 hertz — 3 phase
¡Rated in accordance with ARI Standard 210/240 and certified to ARI; 95_F (35_C) outdoor air temperature and 80_F (27_C) db/67_F (19_C) wb entering evaporator air; mini-
mum external duct static pressure.
©Sound Rating Number rated in accordance with test conditions included in ARI Standard 270.
¢Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. Maximum usable output of motors
furnished by Lennox are shown. In Canada, nominal motor output is also maximum usable motor output. If motors of comparable output are used, be sure to keep within the
service factor limitations outlined on the motor nameplate.
NOTE — Net capacity includes evaporator blower motor heat deduction. Gross capacity does not include evaporator blower motor heat deduction.