Installation - Operation - Maintenance manual (IOM) • AIR COOLED CHILLERS & SPLIT UNITS - 0105-E • 7 •
INSTALLATION - TRANSPORT - HANDLING
3. INSTALLATION
3.1 - Transport - Handling
3.1.1 - Controls and delivery checks
On receipt of a new equipment please check the following points. It is the customer’s responsibility to ensure that
the products are in good working order (fill the check list page 48):
- The exterior has not been damaged in any way.
- The lifting and handling equipment are suitable for the equipment and comply with the specifications of the
handling instructions enclosed here-in.
- Accessories ordered for on site installation have been delivered and are in good working order.
- If the unit is delivered with its operating charge of refrigerant, that there has been no leakage (use an electronic
detector).
- The equipment supplied corresponds to the order and matches the delivery note.
If the product is damaged, exact details must be confirmed in writing by registered post to the shipping company
within 48 hours of delivery (working days).
A copy of the letter must be addressed to LENNOX and the supplier or distributor for information purposes.
Failure to comply will invalidate any claim against the shipping company.
Please be reminded that LENNOX is not responsible for off-loading and positioning.
3.1.1.1 : Unit Nameplate
The rating plate provides a complete reference for the model and ensures that the unit corresponds to the model
ordered. It states the electrical power consumption of the unit on start-up, its rated power and its supply voltage.
The supply voltage must not deviate beyond +10/-10 %.
The start-up power is the maximum value likely to be achieved for the specified operational voltage. The customer
must have a suitable electrical supply. It is therefore important to check whether the supply voltage stated on the
unit's rating plate is compatible with that of the mains electrical supply. The rating plate also states the year of
manufacture as well as the type of refrigerant used and the required charge for each compressor circuit.
3.1.2 - Storage