EasyManuals Logo
Home>Lennox>Air Conditioner>MPB012S4S

Lennox MPB012S4S Service Manual

Lennox MPB012S4S
168 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #161 background imageLoading...
Page #161 background image
161
31.1. Capacity Request Calculations
TotalcapacityRequest=Σ(Normcode×HP)/10×modifyrate+correction.
T1 Ts
3
1
1
e
c
a
4
2
0
2
3
0
1
f
d
b
Figure 83. Cooling Mode
Capacity Area a b c d e f
Norm Code (N) 3 2 1.5 1 .5 0
Model 9K 12K 18K
HP 1.0 1.2 1.5
NOTE: The nal result is integer.
Plusalltheindoorcapacityrequesttogether,thenmodifyitbyT4.
Whenthereisonlyoneindoorunit:
OutdoorTemperature(T4)
Cooling
>29°C 18°Cto29°C <17°C
>84.2°F 64.4°Fto84.2°F <62.6°F
ModifyRate 100% 60% 40%
Whenthereismorethanoneindoorunit:
OutdoorTemperature(T4)
Cooling
>25°C 17°C-25°C <17°C
>77°F 62.6°F-77°F <62.6°F
ModifyRate 100% 80% 40%
NOTE: The nal result is integer.
Inlowambientcoolingmode,modifyrateisxedas40%.
Accordingtothenalcapacityrequesttoconrmheoperatingfrequency,asfollowingtable.
Frequency(Hz) 0
COOL_
F1
COOL_
F2
...
...
COOL_
15
COOL_
16
Amendatory capacity
demand
0 1 2
...
...
15 16
Meanwhilethemaximumrunningfrequencywillbeadjustedaccordingtotheoutdoorambienttemp.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox MPB012S4S and is the answer not in the manual?

Lennox MPB012S4S Specifications

General IconGeneral
BrandLennox
ModelMPB012S4S
CategoryAir Conditioner
LanguageEnglish

Related product manuals