EasyManuals Logo
Home>Lennox>Indoor Fireplace>MPD Series

Lennox MPD Series User Manual

Lennox MPD Series
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #22 background imageLoading...
Page #22 background image
22
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
LENNOX HEARTH PRODUCTS • MERIT PLUS
®
DIRECT VENT GAS FIREPLACES (MPD33/35/40/45) • INSTALLATION INSTRUCTIONS
TABLE H
H
+H
1
Maximum H Maximum
V Minimum
feet
feet
feet
5
(1.524)
2 (0.610) 1 (0.305)
10
(3.048)
4 (1.219) 2 (0.610)
15
(4.572)
6 (1.829) 3 (0.914)
20
(6.096)
8 (2.438) 4 (1.219)
V + H + H
1
= 40 feet (12.2 m) Max.
H = 8 feet (2.438 meters) Max.
H + H
1
= 20 feet (6.096 meters) Max.
(meters)
(meters)
(meters)
H
+ H
1
Maximum
V Minimum
feet
feet
3
(0.914) Elbow Only
5
(1.524)
1 (0.305)
10
(3.048)
2 (0.610)
15
(4.572)
3 (0.914)
20
(6.096)
4 (1.219)
V +
H
+ H
1
= 40 feet (12.2 m) Max.
H
+ H
1
= 20 ft. (6.096 m) Max.
TABLE J
(meters)
(meters)
HORIZONTAL VENT FIGURES/TABLES (continued)
Figure 38: Rear Vent—TWO 90-DEGREE ELBOWS
Figure 39: Top Vent—TWO 90-DEGREE ELBOWS
Square termination (SV4.5HT-2) shown.
See Table 9 on Page 21 as an aid in venting component selection for a particular range
of exterior wall thicknesses.
Note: Install the U-shaped vent restrictor in any vent run with more than 8 ft of vertical
rise (See Page 13).
Square termination (SV4.5HT-2) shown.
Example: If 20 feet of (H) horizontal vent run is needed, then 4
feet minimum of (V) vertical vent will be required.
This table shows a 1 (V) to 5 (H) ratio. For every 1 foot of (V)
vertical, you are allowed 5 feet of (H) horizontal run, up to a
maximum horizontal run of 20 feet.
See Table 9 on Page 21 as an aid in venting component
selection for a particular range of exterior wall thicknesses.
Note: Install the U-shaped vent restrictor in any vent run with
more than 8 ft of vertical rise (See Page 13).
Example: If 20 feet of (H) horizontal vent run is
needed, then 4 feet minimum of (V) vertical vent
will be required.
This table shows a 1 (V) to 5 (H) ratio. For every
1 foot of (V) vertical, you are allowed 5 feet of (H)
horizontal run, up to a maximum horizontal run of
20 feet.
An elbow is acceptable as 1 foot of vertical
rise except where an elbow is the only vertical
component in the system. See Figure 36.
V
H
H
1
Ceiling Firestop/Spacer
SV4.5VF*
Wall Firestop/Spacer
SV4.5HF**
*When using Secure Flex, use
Ceiling Firestop/Spacer SF4.5VF.
**When using Secure Flex, use
Wall Firestop/Spacer SF4.5HF.
Wall Firestop/Spacer
SV4.5HF**
H
1
V
H
Ceiling
Firestop/Spacer
SV4.5VF*
Wall Firestop/
Spacer
SV4.5HF**
*When using Secure Flex , use
Ceiling Firestop/Spacer SF4.5VF.
**When using Secure Flex, use
Wall Firestop/Spacer SF4.5HF.
®

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox MPD Series and is the answer not in the manual?

Lennox MPD Series Specifications

General IconGeneral
BrandLennox
ModelMPD Series
CategoryIndoor Fireplace
LanguageEnglish

Related product manuals