TS − 3 to 5 Ton R−410A Air Conditioners / Page 7
INSTALLATION CLEARANCES − INCHES (MM)
NOTES:
Service clearance of 30 in. (762 mm) must be maintained on one of
the sides adjacent to the control box.
Clearance to one of the other three sides must be 36 in. (914 mm)
Clearance to one of the remaining two sides may be 12 in. (305 mm)
and the final side may be 6 in. (152 mm).
A clearance of 24 in. (610 mm) must be maintained between two units.
48 in. (1219 mm) clearance required on top of unit.
See
NOTES
See NOTES
See NOTES
See
NOTES
CONTROL
BOX
OUTDOOR SOUND DATA
1
Unit
Model No
Octave Band Sound Power Levels dBA, re 10
−12
Watts
Center Frequency − HZ
1
Sound Rating
Number (dB)
M
o
d
e
l
N
o.
125
250 500 1000 2000 4000 8000
N
um
b
er
(dB)
TSA036S4 70.5 67.5 69.5 72.5 69.5 63 59 76
TSA042S4 74 76.5 76.5 75.5 72 68 63.5 80
TSA048S4 73.5 76 76 76.5 72.5 69.5 64.5 80
TSA060S4 73.5 74.5 77 75 72 69 64.5 80
NOTE − the octave sound power data does not include tonal correction.
1
Tested according to ARI Standard 270 test conditions.