EasyManuals Logo
Home>Lennox>Air Conditioner>VPA048H4

Lennox VPA048H4 User Manual

Lennox VPA048H4
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #15 background imageLoading...
Page #15 background image
15
8. After refrigerant piping has been installed and checked
for leaks, apply insulation over all ared connections.
See Figure 20.
Outside
Diameter
Recommended
Torque
No torque wrench
available
Finger tighten and
use an appropriately
sized wrench to turn
an additional:
Inches
3/8” 26 ft.-lb. (35 N-m) 1/2 turn
3/4” 60 ft.-lb. (81 N-m) 1 turn
Table 2. Flare Nut Torque Recommendations
Figure 20. Insulate Flared Connections
UNIT
BASE
INSULATE ALL FLARED CONNECTIONS
TO PREVENT CONDENSATION
A
B
CANT ON THE OUTSIDE OF
THE FLARE
MALE FLARE
CONNECTION
Figure 18. Making Connections
(Male to Female Connection)
Figure 19. Tighten Flare Nut
6. Once snug, continue another half-turn on each
nut which should create a leak-free joint. A torque
wrench may be used to tighten are nuts using table
2 recommendations. See Figure 19. Do not over-
tighten a ared joint. Flared connections should
always be accessible and must be insulated to
prevent condensation.
7. Branch pipe connections may be brazed. It is
necessary to purge the pipes with nitrogen during
brazing to avoid oxidation which may block the
refrigerant piping.
IMPORTANT
The compressor in this unit contains PVE
oil (Polyvinylether). PVE oil is formulated for
hydro uorocarbon (HFC) refrigerants, such as R-
410a, which this system contains. While it may have
some miscibility properties with mineral-based oil
and POE oil (Polyolester), it is not recommended to
mix PVE oil with any other type of refrigerant oil.
IMPORTANT
Always use two wrenches when tightening are
nuts to avoid twisting refrigerant piping. DO
NOT over-tighten are nuts.
NOTE - Always slide a are nut onto the eld-provided
refrigerant piping before aring the lines.
1. The seal on the unit refrigerant piping connections
should remain in place until the last possible moment.
This will prevent dust or water from getting into the
refrigerant piping before it is connected.
2. Remove the are nuts from the connections on the
unit and discard the seal from each of the piping
connections.
3. Slide the are nuts onto the ends of the eld-provided
refrigerant piping before using a suitable aring tool to
are the end of the copper pipe.
4. Apply recommended R-410A refrigerant lubricant to
the outside of the ared refrigerant lines (Figure 18-
A).
5. Align the threaded connections with the ared
refrigerant lines. Tighten the are nuts lightly at rst to
obtain a smooth match (Figure 18-B).
To Outdoor unit
To Indoor Unit
Backup
Wrench
Torque
Wrench

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox VPA048H4 and is the answer not in the manual?

Lennox VPA048H4 Specifications

General IconGeneral
BrandLennox
ModelVPA048H4
CategoryAir Conditioner
LanguageEnglish

Related product manuals