Page 30
XP17
SEE NOTE
Outdoor control is in IDLE mode
(No heating or cooling demand)
To enter unit capacity or fan
profile configuration, push
and hold button next to single
character display until dash
symbol appears and
immediately release button.
Once dash starts blinking,
proceed to next step.
Turn room thermostat
to OFF
Push and hold button until the solid
 or  sequence is displayed on
the seven-segment display and then
immediately release the button. This
configuration sequence allows the
installer to select a unit type
(number / letter combination) that
matches the outdoor unit type and
number of stages.
If three horizontal bars display in any part of the 7-segment
display string during power-up, the outdoor control did not
store that configuration (unit type, capacity or fan profile). If
this occurs, the configuration sequence for that section of the
string must be repeated.
Yes
No
During power up of the outdoor control, the seven-segment display will show the
stored number of stages unit type, capacity and outdoor fan speed.
PAUSE PAUSE
Either the  or  sequence
will repeat 5 times and if a
selection is not made the
control will return to idle mode.
Press and hold the button
during the  or  cycling
display.
NOT
SELECTED
SELECTED
Configuring Unit Capacity or Fan Profile
Power-up - Unit capacity (two-digit number) and displayed
represents unit size code (outdoor unit capacity).
Unit Capacity Code
12
18
24
30
36
42
48
60
1-TON
1-1/2-TON
2-TON
2-1/2-TON
3-TON
3-1/2-TON
4-TON
5-TON
Fan Profile Code (see notes)
SELECTED
NOT
SELECTED
2-Stage Heat Pump Capacity (3-Ton) Fan Profile
UNIT CAPACITY
FAN PROFILE
1. When the correct unit capacity or fan profile is
displayed, release button immediately. [Dis
play will start blinking]
2. Push and hold button until selection stops
flashing during one of the three cycles. [Re
lease push button]
3. If selection is not made during those three
cycles the control will return to idle mode.
The outdoor control will store unit type in memory and will automati
cally exit the configuration and reset control.
During initial power up, the number of stages / unit type, unit
capacity and outdoor fan speed will appear on the 7-segment
display.
Units with EBM motors - The fan motor RPM must be field
set or three bars will appear in the fan profile string section of
the 7-segment display. The factory default is 700 RPM.
EBM fan motor
with blades
NOTE
If three horizontal bars display in any part of the 7-segment
display string sections during power-up, the outdoor control
did not store that configuration (unit type, capacity or fan
RPM). If this happens, the configuration sequence for that
section of the string must be repeated.
SEE NOTE 1
See table 11 for
fan profile.
SEVEN-SEGMENT
DISPLAY
PUSH BUTTON
OUTDOOR CONTROL

Other manuals for Lennox XP21 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox XP21 Series and is the answer not in the manual?

Lennox XP21 Series Specifications

General IconGeneral
BrandLennox
ModelXP21 Series
CategoryHeat Pump
LanguageEnglish

Related product manuals