Page 78
XP17
Use WEIGH IN method for adding initial refrigerant charge, and then use SUBCOOLING method for for
verifying refrigerant charge.
WEIGH IN
Liquid Line
Set Diameter
Ounces per 5 feet (g per 1.5 m)
adjust from 15 feet (4.6 m) line set*
3/8” (9.5 mm)
3 ounce per 5' (85 g per 1.5 m)
*If line length is greater than 15 ft. (4.6 m), add this amount.
If line length is less than 15 ft. (4.6 m), subtract this amount.
Refrigerant Charge per Line Set Length
NOTE — The exampled nameplate is for illustration purposes only. Use data listed on actual unit
nameplate for charging.
CHARGING METHOD
NOTE — Insulate liquid line when it is routed through areas where the surrounding ambient
temperature could become higher than the temperature of the liquid line or when pressure drop is equal
to or greater than 20 psig.
CALCULATING SYSTEM CHARGE FOR OUTDOOR UNIT VOID OF CHARGE
If the system is void of refrigerant, first, locate and repair any leaks and then weigh in the refrigerant charge into the
unit. To calculate the total refrigerant charge:
Amount specified on
nameplate
Adjust amount. for variation
in line set length listed on
line set length table below.
Additional charge specified
per indoor unit match-ups on
unit charging sticker.
Total charge
+
+
=
Figure 49. Using HFC-410A Weigh In Method