Technical Data
UOMu_^MVMO 3-1
3 Technical data
3.1 General data/application conditions
Field Values
Vibration resistance Germanischer Lloyd, general conditions
Humidity class Humidity class F without condensation (average relative humidity 85 %)
Permissible
during transport of the controller: -25 °C ¼ +70 °C
temperature ranges
during storage of the controller: -25 °C ¼ +55 °C
during operation of the controller: 0 °C ¼+40 °C
+40
°C ¼ +50 °C
without power derating
with power derating
Permissible
installation height h
h ≤ 1000 m.a.m.s.l
1000 m a.m.s.l
< h ≤ 4000 m a .m.s.l
without power derating
with power derating
Degree of pollution VDE 0110 part 2 pollution degree 2
Noise emission Requirements acc. to EN 50081-2, EN 50082-1, IEC 22G-WG4 (Cv) 21
Limit value class A to EN 55011 (industrial area) with mains filter
Limit value class B to EN 55022 (residential area) with mains filter and installation into
control cabinet
Noise immunity
Limit values maintained usig mains filter
Requirements according to E N 50082-2, IEC 22G-WG4 (Cv) 21
Requirements Standard Severities
ESD EN61000-4-2 3, i.e. 8 kV with air discharge
6 kV with contact discharge
RF interference(enclosure) EN61000-4-3 3, i.e. 10 V/m; 27¼1000 MHz
Burst EN61000-4-4 3/4, i.e. 2 kV/5 kHz
Surge
(Surge on mains cable)
EN 61000-4-5 3, i.e. 1.2/50 μs,
1 kV phase-phase,
2 kV phase-PE
Insulation strength Overvoltage category III according to VDE 0110
Packaging
(DIN 4180)
Dust packaging
Type of protection IP20
NEMA 1: Protection against contact
Approvals CE: Low Voltage Directive
Electromagnetic compatibility
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com