8
Mechanical installaon
Operang Instrucons i510-Cabinet
B
H1
H
E2
E1
X
X
H: Device height X: Number of top/boom xings
B: Device width (lower fastening not visible)
T: Device depth X - X: Hole spacing over center of device
H1: Hole dimension for top/boom xing E1: Top mounng clearance
E2: Bottom mounting clearance
4 Mechanicalinstallaon
4.1 Dimensions and assembly
Rated power
[kW]
Weight
[kg]
H
[mm]
W
[mm]
D
[mm]
H1
[mm]
X [screws + hole
spacing]
E1
[mm]
E2
[mm]
1-phasemainsconnecon230/240V;withintegratedRFIlter
I51AExxxB 0.25 – 0.37 0.75 155 60 130 165 1 - M5 50 50
I51AExxxB 0.55 – 0.75 0.95 180 60 130 190 1 - M5 50 50
I51AExxxB 1.1 – 2.2 1.35 250 60 130 260 1 - M5 50 50
1-/3-phasemainsconnecon230/240V;withoutintegratedRFIlter
I51AExxxD 0.25 – 0.37 0.75 155 60 130 165 1 - M5 50 50
I51AExxxD 0.55 – 0.75 0.95 180 60 130 190 1 - M5 50 50
I51AExxxD 1.1 – 2.2 1.35 250 60 130 260 1 - M5 50 50
I51AExxxC 4.0 – 5.5 2.1 250 90 130 260 2 30 M5 50 100
Three-phasemainsconnecon400V/480V–Heavyduty;withintegratedRFIlter
I51AExxxF 0.37 0.75 155 60 130 165 1 - M5 50 50
I51AExxxF 0.55 – 0.75 0.95 180 60 130 190 1 - M5 50 50
I51AExxxF 1.1 – 2.2 1.35 250 60 130 260 1 - M5 50 50
I51BExxxF 3.0 – 4.0 1.35 250 60 130 260 1 - M5 50 50
I51AExxxF 3.0 – 5.5 2.3 250 90 130 260 2 30 M5 50 100
I51AExxxF 7.5 – 11.0 3.7 276 120 130 285 2 60 M5 50 100
Three-phasemainsconnecon400V/480V-Lightduty;withintegratedRFIlter
I51AExxxF 4.0 – 7.5 2.3 250 90 130 260 2 30 M5 50 100
I51AExxxF 11.0 – 15.0 3.7 276 120 130 285 2 60 M5 50 100