DB DB CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC CA SHC
70 21 4.7 3.5 5.2 3.1 - - - -
--
----
--
--
----
--
----
----
--
--
--
--
--
--
--
----
--
--
----
--
--
--
--
--
--
--
--
--
--
--
--
--
------ ----
---------- ----
-------- ----
-------- ----
------ ----
---- ----
-- ----
-- - -
-- - -
--
-------- ----
-------- ----
------ ----
---- ----
-- ----
-- - -
-- - -
73 23 4.6 4.1 5.0 3.7 7.8 3.6
77 25 4.6 4.5 4.9 4.3 7.7 4.2
81 27 4.9 4.9 6.9 4.8 10.4 4.6
84 29 6.6 5.4 9.9 5.2 12.9 4.6
88 31 6.3 6.1 9.0 5.7 12.5 5.2 14.2 5.1
91 33 8.8 6.3 12.2 5.8 13.6 5.5 15.2 4.7
96 35 8.6 6.9 11.8 6.4 13.1 5.9 14.9 5.3
99 37 11.0 6.9 12.7 6.5 14.3 5.9 16.2 5.4
104 40 10.6 7.9 12.4 7.5 13.9 6.8 15.9 6.4 17.4 5.5
DB DB DB WB DB WB DB WB DB WB DB WB DB WB DB
WB
DB WB DB WB
70 21 11.8 9.9 12.7 11.8
73 23 11.9 10.0 13.0 12.0 13.5 12.7
77 25 12.0 10.1 13.3 12.0 13.7 12.8
81 27 13.8 12.0 14.0 13.5 14.7 14.0
84 29 14.2 13.8 14.8 14.4 16.7 15.7
88 31 14.3 14.0 15.5 15.2 16.9 16.0 17.5 17.4
91 33 15.7 15.3 17.2 16.2 18.2 17.9 20.5 19.5
96 35 15.8 15.5 17.5 16.5 18.9 18.2 20.7 19.7
99 37 17.7 17.2 19.2 18.5 20.9 20.1 22.5 21.6
104 40 17.9 17.5 19.5 18.7 21.2 20.3 22.5 21.7 25.2 25.1
30
WB 32.0 35 WB
82
WB
86
WB
90
WB
95
WB
17 WB 20 WB 23 WB 26 WB 28 WB
Outdoor
air tempreture
59
WB
73
WB
63
WB
69
WB
79
WB
73
WB 79 WB 82 WB 86 WB
Outdoor
air tempreture
59
WB 63 WB 69 WB 90 WB 95 WB
15
WB 17 WB 20 WB 23 WB 26 WB 28 WB 30 WB 32.0 35 WB
DB DB
18 -9
27 -3
32 0
37 3
45 7
52 11
59 15
64 18
68 20
DB DB
18 -9
27 -3
32 0
37 3
45 7
52 11
59 15
64 18
68 20
43.5
-------43.1
- - - 43.2---
43.7
- - 42.8 43.0 -
---
---
43.2---
-
- - - 42.6 43.2 43.3 - -
42.7 - - ---42.1
-
-39.2------
--
DB
38.7------
------
10
WB
14
WB
DB DB DB
ARNU483BRZ4
Cooling
Heating
1. Outlet Air Temperature
Note) CA: Total Capacity (KW), SHC: Sensible Heat Capacity (kW)
WB: Wet Bulb(℃), DB: Dry Bulb(℃)
1. The data shown in the graph illustrates the supported operating ranges underthe following conditions:
- Indoor and Outdoor Unit
- Effective piping length: 295.3 inch
- Height differential: 0 inch
2. The actual temperature may not match the temperature setting under some circumstances due to the out-
door-air processing load or mechanical protection controls.
3. The system will not operate in fan mode when the outdoor air temperature is 23 °F or below.