Operation Details
2. Operation Details
DISPLAY
1) High quality LCD remote controller supplied
Operation Indicator
• On while in appliance operation, off while in appliance pause
Timer Indicator
• On while in timer mode (on/off) and in sleep timer mode, off when timer mode is completed or canceled
Defrost Indicator
• Off except when hot start during heating mode operation or while in defrost control.
Plasma Indicator
• On while in plasma mode, off while plasma mode is canceled.
Auto restart Indicator
• On while auto restart mode, off while auto restart mode is canceled.
Auto restart
• In case the power comes on again after a power failure, Auto Restarting Operation is the function to operate
procedures automatically to the previous operating conditions.
If your want to use this operation, press the Auto Restart Button.
Power(Forced Operation)
• Operation starts, when this button is pressed and stops when you press the button again.
n Cooling Mode Operation
•
When the intake air temperature reaches 0.5°C(33°F) below the setting temp, the compressor and the outdoor
fan stop.
• When it reaches 0.5°C
(33°F)
above the setting temp, they start to operate again.
Compressor ON Temp=> Setting Temp+0.5°C
(33°F)
Compressor OFF Temp => Setting Temp-0.5°C
(33°F)
• While in compressor running, operating with the airflow speed set by the remote controller. While in compres-
sor not running, operating with the low airflow speed regardless of the setting.
n Healthy Dehumidification Mode
• When the dehumidification operation input by the remote controller is received, the intake air temperature is
detected and the setting temp is automatically set according to the intake air temperature.
26°C(78°F) ≤ Intake Air Temp => 25°C(76°F)
24°C(76°F) ≤ Intake Air Temp < 26°C(78°F) => Intake Air Temp-1°C(34°F)
18°C(64°F) ≤ Intake Air Temp < 24°C(76°F) => Intake Air Temp-0.5°C(33°F)
Intake Air Temp < 18°C(64°F) => 18°C(64°F)
• While in compressor off, the indoor fan repeats low airflow speed and pause.
• While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidification
operation and 4-min compressor off repeat
Compressor ON Temp. => Setting Temp+0.5°C(33°F)
Compressor OFF Temp. => Setting Temp-0.5°C(33°F)
• In 10-min dehumidification operation, the indoor fan operates with the low airflow speed.
n Heating Mode Operation
Function of Controls