Operating Manual V25/09.2019
Ventus / Ventus-X / V200A
Chapter 20 Appendix 57
For details of the SDI-12 protocol please refer to the above mentioned standard document.
Following commands are available for the
Ventus
:
Befehl
Funktion
?!
Address search (Wildcard request, one device only on bus!)
a!
Request device active?
aI!
Request device identification
aAb!
Address change to b ( 0 … 9, A …Z, a … z)
aM!
Measurement, minimal base data set
aM1!
Measurement, Temperature Values
aM2!
Measurement: Wind Values
aM3!
Measurement: Air Pressure Values
aMC!
Measurement,minimal base data set, transmit values with CRC
aMC1!
aMC3!
Measurement, (value assignment as for aMn! commands), transmission with
CRC
aC!
Concurrent measurement, complete base data set
aC1! …
aC3!
Concurrent measurement, (value assignment as for aMn! Commands),
extended data set
aCC!
Concurrent measurement, complete data set,, transmit values with CRC
aCC1!
aCC3!
Concurrent measurement, complete data set,, (value assignment as for aMn!
Commands), extended data set , transmit values with CRC
aD0!
Data request buffer 0
aD1!
Data request buffer 1
aD2!
Data request buffer 2
aD3!
Data request buffer 3
aD4!
Data request buffer 4
aR0!
Data request from continuous measurement, data set 0
aR1!
Data request from continuous measurement, data set 1
aR2!
Data request from continuous measurement, data set 2
aR3!
Data request from continuous measurement, data set 3
aR4!
Data request from continuous measurement, data set 4
aRC0!
Data request from continuous measurement, data set 0 with CRC
aRC1!
Data request from continuous measurement, data set 1 with CRC
aRC2!
Data request from continuous measurement, data set 2 with CRC
aRC3!
Data request from continuous measurement, data set 3 with CRC
aRC4!
Data request from continuous measurement, data set 4 with CRC
aV!
Command verification: Evaluate sensor status and heating temperatures, data
request with aD0!, aD1!
aXU<m/u>!
Selection of the unit system for SDI12 data
aXH+nnnn!
Adjust the local altitude for calculation ot relative air pressure
aXMn!
Select the heating mode of the device (
aXR!
Device Reset
Note: The examples in the following sections use italics to print the requests from the logger (