EasyManuals Logo
Home>Manitowoc>Ice Maker>CVDT1200

Manitowoc CVDT1200 Technician's Handbook

Manitowoc CVDT1200
212 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #152 background imageLoading...
Page #152 background image
152 Part Number: 000015431 Rev01 5/19
LOW PRESSURE CUTOUT (LPCO) CONTROL
FUNCTION
Supplies or interrupts power to the compressor time delay
when suction pressure rises above or falls below setpoint.
The LPCO control is closed at pressures above setpoint and
opens at pressures below setpoint.
Specifications
Cut-Out Cut-In
R404A 12 psig ±3 35 psig ±5
R410A 20 psig ±3 50 psig ±5
CHECK PROCEDURE
Opening the LPCO will initiate the 5 minute compressor
time delay relay. Repeated opening/closing or failure to
close will result in an E01 long freeze error.
CHECK PROCEDURE
1. Connect manifold gauges to ice machine.
2. Hook voltmeter in parallel across the fan cycle control,
leaving wires attached.
3. Refer to chart below.
LPCO Setpoint Reading Should Be LPCO Contact Position
Above Cut-In 0 Volts Closed
Below Cut-Out Line Voltage Open

Table of Contents

Other manuals for Manitowoc CVDT1200

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Manitowoc CVDT1200 and is the answer not in the manual?

Manitowoc CVDT1200 Specifications

General IconGeneral
BrandManitowoc
ModelCVDT1200
CategoryIce Maker
LanguageEnglish

Related product manuals