Part Number STH042 3/14 55
* Condenser Fan Motor: The fan motor is wired through a fan cycle pressure control; therefore, it may cycle on and off.
** The water fill valve is de-energized by the control board 1 minute after the freeze cycle starts - The control board will energize the water inlet
valve for 7 seconds one last time, 3 minutes into the freeze cycle, regardless of float position.
4. Freeze
ON OFF ON** OFF ON OPEN THEN
CLOSED
CLOSED THEN
OPEN
Until
Harvest
Float Switch
closes for
10 continual
seconds
Harvest
Sequence
5. Water Purge
OFF ON OFF ON FOR 20
SECONDS
THEN OFF
ON CLOSED CLOSED 20 seconds
6. Harvest
OFF ON OFF OFF ON CLOSED CLOSED
Bin switch
activation
7. Automatic
Shut-off
OFF OFF OFF OFF OFF CLOSED CLOSED
Until bin
switch
re-closes