EasyManuals Logo
Home>Manitowoc>Ice Maker>QM20

Manitowoc QM20 User Manual

Manitowoc QM20
236 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #176 background imageLoading...
Page #176 background image
176 Part Number 80-01111-9 7/10
Compressor Electrical Diagnostics
The compressor does not start or will trip repeatedly
on overload.
CHECK RESISTANCE (OHM) VALUES
NOTE: Compressor windings can have very low ohm
values. Use a properly calibrated meter.
Perform the resistance test after the compressor
cools. The compressor dome should be cool enough
to touch (below 120°F/49°C) to ensure that the
overload is closed and the resistance readings will be
accurate.
SINGLE PHASE COMPRESSORS
1. Disconnect power from the condensing unit and
remove the wires from the compressor terminals.
2. The resistance values between C and S and
between C and R, when added together should
equal the resistance value between S and R.
3. If the overload is open, there will be a resistance
reading between S and R, and open readings
between C and S and between C and R. Allow the
compressor to cool, then check the readings
again.
CHECK MOTOR WINDINGS TO GROUND
Check continuity between all three terminals and the
compressor shell or copper refrigeration line. Scrape
metal surface to get good contact. If continuity is
present, the compressor windings are grounded and
the compressor should be replaced.
To determine if the compressor is seized check the
amp draw while the compressor is trying to start.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Manitowoc QM20 and is the answer not in the manual?

Manitowoc QM20 Specifications

General IconGeneral
BrandManitowoc
ModelQM20
CategoryIce Maker
LanguageEnglish

Related product manuals