24 Part Number 80-01111-9 7/10
Ice Machine Clearance Requirements
*NOTE: The ice machine may be built into a cabinet.
There is no minimum clearance requirement for the
top or left and right sides of the ice machine. The listed
values are recommended for efficient operation and
servicing only.
Ice Machine Heat of Rejection
* B.T.U./Hour
** Because the heat of rejection varies during the ice making cycle,
the figure shown is an average.
Ice machines, like other refrigeration equipment, reject
heat through the condenser. It is helpful to know the
amount of heat rejected by the ice machine when
sizing air conditioning equipment where self-contained
air-cooled ice machines are installed.
Self-contained
Air-cooled
Self-contained
Water-cooled
Top/Sides 5" (127 mm)* 5" (127 mm)*
Back 5" (127 mm)* 5" (127 mm)*
Series
Ice Machine
Heat of Rejection*
Air Conditioning** Peak
SM50 1145 2300
QM20 1450 2100
QM30 1600 2350
QM45 1750 2600
Q130 2100 3300
Q170 2200 2600
Q210 2400 3400
Q270 3800 6000