Installation Instructions Section 2
2-8
Part Number 000002477 3/08
Location of CVD Condensing Unit
The location selected for the CVD Condensing Unit must
meet the following criteria. If any of these criteria are not
met, select another location.
The air temperature must be at least -20°F (-28.9°C)
but must not exceed 130°F (54.4°C).
CVD675/CVD1185/CVD2085 Only - The air
temperature must be at least -20°F (-28.9°C) but
must not exceed 120°F (48.9°C).
CVD1486 Only- The air temperature must be at least
50°F (10°C) but must not exceed 110°F (43°C).
The location must not allow exhaust fan heat and/or
grease to enter the condenser.
The location must not obstruct airflow through or
around the condensing unit. See below for clearance
requirements.
Condensing Unit Clearance Requirements
CVD675/CVD885/CVD1085/CVD1185/CVD2085
Top/Sides
There is no minimum clearance required, although 6”
(15.2 cm) is recommended for efficient operation and
servicing only.
Front/Back
48” (122 cm)
CVD1285/CVD1485/CVD1885
Top/Sides
There is no minimum clearance required, although 6”
(15.2 cm) is recommended for efficient operation and
servicing only.
Front
24” (61 cm)
Back
48” (122 cm)
CVD1486 ONLY
Top - 5” (12.7 cm) is required for efficient operation and
servicing.
Front/Back/Sides - 12” (30.5 cm)

Table of Contents

Other manuals for Manitowoc S model

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Manitowoc S model and is the answer not in the manual?

Manitowoc S model Specifications

General IconGeneral
BrandManitowoc
ModelS model
CategoryIce Maker
LanguageEnglish

Related product manuals