EasyManuals Logo
Home>Manitowoc>Ice Maker>SD0422A

Manitowoc SD0422A User Manual

Manitowoc SD0422A
300 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #180 background imageLoading...
Page #180 background image
180 Part Number 80-1479-3 7/10
CLEANUP PROCEDURE
Mild System Contamination
1. Replace any failed components.
2. If the compressor is good, change the oil.
3. Replace the liquid line drier.
NOTE: If the contamination is from moisture, use
heat lamps during evacuation. Position them at the
compressor, condenser and evaporator prior to
evacuation. Do not position heat lamps too close to
plastic components, or they may melt or warp.
4. Follow the normal evacuation procedure, except
replace the evacuation step with the following:
A. Pull vacuum to 1000 microns. Break the
vacuum with dry nitrogen and sweep the
system. Pressurize to a minimum of 5 psig
(35 kPa, .35 bar).
B. Pull vacuum to 500 microns. Break the
vacuum with dry nitrogen and sweep the
system. Pressurize to a minimum of 5 psig
(35 kPa, .35 bar).
C. Change the vacuum pump oil.
D. Pull vacuum to 500 microns. Run the vacuum
pump for 1/2 hour on self-contained models,
1 hour on remotes.
NOTE: You may perform a standing vacuum test to
make a preliminary leak check. You should use an
electronic leak detector after system charging to be
sure there are no leaks.
5. Charge the system with the proper refrigerant to
the nameplate charge.
6. Operate the ice machine.
Important
Dry n itrogen i s re commended fo r this p rocedure.
This will prevent CFC release.

Table of Contents

Other manuals for Manitowoc SD0422A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Manitowoc SD0422A and is the answer not in the manual?

Manitowoc SD0422A Specifications

General IconGeneral
BrandManitowoc
ModelSD0422A
CategoryIce Maker
LanguageEnglish

Related product manuals