EasyManuals Logo
Home>McQuay>Air Handlers>RDS 800C

McQuay RDS 800C User Manual

McQuay RDS 800C
122 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #13 background imageLoading...
Page #13 background image
McQuay IM 987 13
Introduction
SPS2
Static pressure
sensor duct #2
Converts static pressure
signals to voltage signals
and sends them to
MicroTech III controller
N/A
Main control
box
N/A
0–5" wc
(0–1245.4 Pa)
1–6 V (dc) out
N/A 049545007
Static pressure
sensor: building
(space) pressure
Converts static pressure
signals to voltage signals.
N/A
Main control
box
N/A
-025–0.25" wc
(-62.3–62.3
Pa)
1–5 V (dc) out
N/A 049545006
S1
System switch
Shuts off entire control circuit
(except crankcase heaters)
N/A
Main control
box
N/A N/A N/A 001355000
S7
ON-OFF-AUTO
switch
Used to manually switch unit
N/A
Main control
box
N/A N/A N/A
Table 2: Controls, Settings, and Functions (continued)
Symbol Description Function Reset Location Setting Range Differential Part no.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the McQuay RDS 800C and is the answer not in the manual?

McQuay RDS 800C Specifications

General IconGeneral
BrandMcQuay
ModelRDS 800C
CategoryAir Handlers
LanguageEnglish

Related product manuals