Mercury Security Corporation © 2009 MR16out DOC 10107-0010 REV 2.01 Page 3
6. DIP Switch and Jumper Usage:
Switches 1 to 5 select the device address. Switch 6 and 7 select the communication baud rate. Switch 8
enables encrypted communication. All other configuration settings are set via host software.
115,200 BPS, See note 1 below.
Encrypted communication not required
See note 2 below.
Encrypted communication required
See note 2 below.
Note 1: Firmware revisions prior to 1.30.1, this setting is 2,400 BPS.
Note 2: Firmware revisions prior to 1.30.1, SW8 is not defined. Set to the OFF position.