Mercury Security Corporation © 2009 MR16out DOC 10107-0010 REV 2.01 Page 2
3. Communication Wiring:
The MR16out communicates to a controller via a 2-wire RS-485 interface. The interface allows multi-drop
communication on a single bus of up to 4,000 feet (1,200 m). Use twisted pair (minimum 24 AWG) with
shield for the communication line.
Install the following jumpers for the RS-485 interface according to the selected configuration:
4. Inputs for Cabinet Tamper/Power Fault:
Input CT and input BA are used for monitoring cabinet tamper and power failure with normally closed
contacts. These two inputs are for contact closure monitoring only, and do not use EOL resistor(s). If
these inputs are not used, install a short piece of wire at the input to indicate a safe condition.
5. Relay Outputs:
The following diagrams show typical use of the relay. A DC power source is recommended whenever
possible. Transient clamping must be provided to protect the contacts and to reduce EMI emission. Use
sufficiently large wires for the load current to avoid voltage loss.
DIODE SELECTION:
DIODE CURRENT RATING > 1 X STRIKE CURRENT
DIODE BREAK DOWN VOLTAGE: 4X STRIKE VOLTAGE
FOR 12Vdc or 24Vdc STRIKE, DIODE 1N4002 (100V /1A)
TYPICAL
MOV SELECTION:
CLAMP VOLTAGE > 1.5 X Vac RMS
FOR 24Vac STRIKE, PANASONIC ERZ-C07DK470
TYPICAL
CT
GND
BA
GND
CABINET
TAMPER
POWER
FAULT
TB9
NC
C
NO
NC
C
NO


NC
C
NO
NC
C
NO

TR+
TR-
R+
R-
GND
2W
4W
2-WIRE
TB10
(ONLY 2-WIRE RS-485 IS SUPPORTED)

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mercury Security MR16out and is the answer not in the manual?

Mercury Security MR16out Specifications

Power IconPower
primary power voltage range12 to 24 Vdc ±10%
primary power maximum current1100 mA
nominal current at 12 Vdc850 mA
nominal current at 24 Vdc450 mA
Relay Contacts IconRelay Contacts
relay contact type16 Form-C
relay contact rating5 A @ 30 Vdc
relay contact resistanceresistive
Operating Environment IconOperating Environment
storage temperature range-55°C to +85°C
operating temperature range0°C to +70°C
humidity range0% to 95% RHNC
Weight and Dimensions IconWeight and Dimensions
dimension width6 in (152 mm)
dimension length8 in (203 mm)
dimension height1 in (25.4 mm)
weight14 oz (400 gm) nominal