4. Installation Details
4.1 Wrench torque sheet for installation
Outside diameter
Torque
Additional tightening torque
mm
inch
N.cm
N.cm
Ф6.35
1/4
1500(153kgf.cm)
1600(163kgf.cm)
Ф9.52
3/8
2500(255kgf.cm)
2600(265kgf.cm)
Ф12.7
1/2
3500(357kgf.cm)
3600(367kgf.cm)
4.2 Connecting the cables
The power cord connection should be
selected according to the following
specifications sheet.
Unit
AWG
1 drive 2 type (18K outdoor unit)
14
1 drive 3 type (27K outdoor unit).
14
1 drive 4 type (36K outdoor unit)
12
1 drive 5 type (48K outdoor unit)
10
For indoor unit and outdoor unit connection
line, 16AWG is ok for all.
4.3 Pipe length and the elevation
Maximum piping length and height difference
1 drive 2
1 drive 3
1 drive 4
1 drive 5
Max. length for all
rooms (m)
40
(131ft)
60
(197ft)
80
(262ft)
80
(262ft)
Max. length for
one IU (m)
25 (82ft)
30 (98ft)
35
(115ft)
35
(115ft)
Max. height
difference between
IU and OU (m)
15
(49.2ft)
15
(49.2ft)
15
(49.2ft)
15
(49.2ft)
Max. height
difference between
IUs (m)
10 (33ft)
10 (33ft)
10 (33ft)
10 (33ft)
Additional refrigerant charge
1 drive 2
1 drive 3
1 drive 4
1 drive 5
Pre-charge pipe
length (m)
15
(49.2ft)
22.5
(73.8ft)
30
(98.4ft)
37.5
(123ft)
Additiona
l
refrigeran
t charge
g
15 x
(length
for all
rooms -
15)
15 x
(length
for all
rooms
22.5)
15 x
(length
for all
rooms -
30)
15 x
(length
for all
rooms
37.5)
oz
0.161
x(length
for all
rooms
49.2)
(0.161
x(length
for all
rooms
73.8)
0.161x(le
ngth for
all rooms
98.4)
.0.161x(le
ngth for
all rooms
123)
Caution:
Refrigerant pipe diameter is different
according to indoor unit to be connected.
When using the extension pipe, refer to the
tables below.
When refrigerant pipe diameter is different
from that of the outdoor unit connector (18K
indoor unit) an additional adapter is required.
Indoor unit
Extension pipe diameter
(mm/inch)
Model
Pipe diameter
(mm/inch)
9K
Liquid
6.35(1/4)
Liquid
6.35(1/4)
Gas
9.52(3/8)
Gas
9.52(3/8)
12K 18K
Liquid
6.35(1/4)
Liquid
6.35(1/4)
Gas
12.7(1/2)
Gas
12.7(1/2)
24K
Liquid
9.52 (3/8)
Liquid
9.52 (3/8)
Gas
15.9(5/8)
Gas
15.9(5/8)
Outdoor unit union diameter (mm/inch)
1 drive 2
Liquid
6.35(1/4) *2
Gas
9.52(3/8) *2
1 drive 3
Liquid
6.35(1/4) *3
Gas
9.52(3/8) *3
1 drive 4
Liquid
6.35(1/4) *4
Gas
9.52(3/8) *3
12.7(1/2) *1
1 drive 5
Liquid
6.35(1/4) *5
Gas
9.52(3/8) *3
12.7(1/2) *2
4.4 First-Time Installation
Air and moisture in the refrigerant system cause
the following problems:
Increases in system pressure
Increases in operating current
Decreases in cooling and heating efficiency
Blocks in capillary tubing caused by moisture
in the refrigerant circuit freezing
Corrosion of parts in the refrigerant system
caused by water
The indoor units and the pipes between
indoor and outdoor units must be tested for
leakages and evacuated to remove gas and
moisture from the system.
Gas leak check with soap water:
Apply soap water or a liquid neutral
detergent on the connections with a soft brush to
check for leakage in the pipe connecting points. If
bubbles emerge, the pipes are leaking.
1. Air Purging Using the Vacuum Pump

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea Advantage Series and is the answer not in the manual?

Midea Advantage Series Specifications

General IconGeneral
BrandMidea
ModelAdvantage Series
CategoryHeat Pump
LanguageEnglish

Related product manuals