7.4.2.14. High temperature protection of compressor top(IDU P2/ODU P0)
Malfunction decision
conditions
If the sampling voltage is not 5V, the LED will display the failure.
Supposed causes
Faulty overload protector
Wiring mistake
System leakage or block
Faulty PCB
Check if the air flow system
of indoor and outdoor units
are obstructed?
Clear up the air inlet and outlet or the heat
exchanger of indoor and outdoor units.
Yes
No
Yes
Yes
Turn off the power supply and turn
it on 10 minutes later.
Check if the temperature
of compressor Top
Is more than 90℃?
No
Check if the refrigerant
system
is normal?
Repair the refrigerant
system .
Replace the outdoor control PCB.
Yes
Check if all the connection, especially
the connection of OLP (Over Load
Protector) sensor is good.
Correct the connection.No
Measure the resistance
between the two ports of
the OLP. Is it zero?
Yes
Replace the OLP.No
Replace the outdoor control PCB.
Yes
No

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea Advantage Series and is the answer not in the manual?

Midea Advantage Series Specifications

General IconGeneral
BrandMidea
ModelAdvantage Series
CategoryHeat Pump
LanguageEnglish

Related product manuals