Product Features 6
For above 18K models:
T2
Setting fan
speed(Turbo)
Low
Breeze
Fan off
TE2
TE3
TE2-6
TE1
TE3-6
TE1-6
NOTE: During temperature rise, medium speed changeover
has no requirement of forced running time . But during
temperature drop, the high speed must be forced to run
for 2 minutes before judging whether to directly turn to
the low speed.
Auto fan action in heating mode:
3.5.3 Outdoor Fan Control:
Outdoor units just have one single fan speed. The
operation of outdoor fan is consistent with the operation
of compressor. Except the following situations:
Evaporator high temperature protection
Defrosting
Current protection.
3.5.4 Defrosting mode
Case 1:
The unit enters defrosting mode according to the
temperature difference between T2 and T1, as well as
the compressor runtime.
In defrosting mode, the compressor continues to run,
the indoor and outdoor motor will cease operation,
the defrost light of the indoor unit will turn on, and
the “ ” symbol is displayed.
If any one of the following conditions is satisfied,
defrosting ends and the machine switches to normal
heating mode:
Compressor current is over than I
defrost
and lasts for
7s
The defrosting time has reached the setting value.
T22°C(3.6°F) after entering defrosting mode for 3
minutes.
After entering defrosting mode for 2 minutes,
check the value of T2. The minimum temperature
of T2 is marked as T2min. If T2-T2min2°C(3.6°F)
during the following 4 minutes, AC will exit
defrosting mode(if T2-15°C(5°F),considers it as
-15°C(5°F)).
Case 2:
The unit enters defrosting mode according to the
value of temperature of T3 and the value range of
temperature change of T3 as well as the compressor
runtime..
In defrosting mode, the compressor continues to run,
the indoor and outdoor motor will cease operation,
the defrost light of the indoor unit will turn on, and
the “ ” symbol is displayed.
If any one of the following conditions is satisfied,
defrosting ends and the machine switches to normal
heating mode:
T3 rises above TC2.
Unit runs for 10 minutes consecutively in defrosting
mode.
3.5.5 Evaporator Temperature Protection
When the evaporator temperature exceeds a preset
protection value, the compressor ceases operation.
3.6 Auto-mode
This mode can be selected with the remote controller
and the setting temperature can be changed between
17°C~30°C(62°F~86°F).
In auto mode, the machine selects cooling, heating, or
fan-only mode on the basis of T (T =T1-TS).
T Running mode
T>A Cooling
B≤∆TA Fan-only
T<B Heating*
Heating*: In auto mode, cooling only models run the fan
Indoor fan will run at auto fan speed.
The unit will choose running mode, when
received the auto signal from the remote controller;
forced-auto mode by pressing manual button;

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea AURORA ONOFF Series and is the answer not in the manual?

Midea AURORA ONOFF Series Specifications

General IconGeneral
BrandMidea
ModelAURORA ONOFF Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals