14.3 Important information for the used
refrigerant
This product has the fluorinated gas it is forbidden to release
to air.
Refrigerant type: R410A; Volume of GWP: 2088;
GWP=Global Warming Potential
Attention:
Frequency of Refrigerant Leak Checks
1) For equipment that contains fluorinated greenhouse gases in
quantities of 5 tonnes of CO
2
equivalent or more,but of less than
50 tonnes of CO
2
equipment,at least every 12 months, or where
a leakage detection system is installed, at least every 24 months.
2) For equipment that contains fluorinated greenhouse gases in
quantities of 50 tonnes of CO
2
equivalent or more,but of less than
500 tonnes of CO
2
equipment,at least every six months, or where
a leakage detection system is installed, at least every 12 months.
3) For equipment that contains fluorinated greenhouse gases in
quantities of 500 tonnes of CO
2
equivalent or more,at least every
three months, or where a leakage detection system is installed,
at least every six months.
4) This air-conditioning unit is a hermetically sealed equipment that
contains fluorinated greenhouse gases.
5) Only certificated person is allowed to do installation, operation
and maintenance.
Model
Refrigerant/kg tonnes CO
2
equivalent
2.40
2.40
2.40
3.60
3.60
3.60
5.01
5.01
5.01
7.52
7.52
7.52
9kW
10kW
12kW
14kW
5kW
7kW
Factory charge
16kW
3.60 7.52