MCAC-RTT6S-201701 Midea R410A Tropical ClimaCreator Series Rooftop Package 220V 3Ph 60Hz
130
until the foregoing switch is turned off. If the foregoing two switches are turned on
concurrently, the emergent shutdown switch shall have preference.
3.5 General display data entries
1) General display data is displayed in all display pages.
Under the interconnected control of the computer or gateway, the data is displayed in
graphic ( ). Otherwise, no data is displayed.
If the centralized controller is connected with the functional module for communication,
the data is displayed in graphics ( ). Otherwise, no data is displayed.
If the centralized controller is connected with the SMS remote control module for
communication, the data is displayed in graphics ( ). Otherwise, no data is displayed.
If the centralized controller is connected with the telephone remote control module for
communication, the data is displayed in graphics ( ). Otherwise, no data is displayed.
In normal operation of the centralized controller, the periodical cycle module
communicates with the network interface module, and the data is displayed
dynamically and cyclically: (blank), , , .
In the centralized control locked status or the keypad locked status, the locking flag ( )
is displayed. After unlocking, it is not displayed. In the centralized controller locked
status or the keypad locked status, the locking flag is displayed constantly. If both of
them are locked concurrently, the locking flag is displayed constantly.
In the setting page, if the selected air conditioner is in the remote controller locked
status (in case of non-single machine operation, as long as one machine is in the
remote controller locked status, it is deemed the locked status), the flag ( ) is
displayed constantly.
If all indoor units lock the cooling mode, this flag ( ) will display, and if all indoor units
lock the heating mode, the flag ( ) will display.
2) Data display handling
Indoor unit code (address) display: display range: 00~63, and with # being luminous
concurrently.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea MRCT-075CWN1-D(C) and is the answer not in the manual?

Midea MRCT-075CWN1-D(C) Specifications

General IconGeneral
BrandMidea
ModelMRCT-075CWN1-D(C)
CategoryAir Conditioner
LanguageEnglish

Related product manuals