V6R VRF 50/60Hz
174
Midea V6R Series Engineering Data Book
Refrigerant leakage sensor connection and settings for MS01
Shut off power before connect the refrigerant leakage sensor to the corresponding port on the MS main board.
Max. 5 refrigerant leakage sensors can be connected to one MS01, and the connection port number of refrigerant
sensor is CN3 ~ CN7 on the main board.
Setting the correct numbers of the connected sensors with the ENC1 in the main control board.
S1‐1 switch should be set to ''ON'' position.
Figure 3-9.7:
Refrigerant leakage sensor connection
9.4 Wiring Example
Figure 3-9.8: Wiring of piping lines and communication wires
Main control board
Refrigerant
leakage sensor
CN4CN5 CN3CN6CN7
Piping Line
Communication Wiring
Outdoor Unit
NO.1 MS box
MS-Outdoor or MS
Outdoor
NO.2 MS01 box
NO.2 MS box
NO.1 MS box
654321
NO.3 MS box
654321
1
NO.3 MS box
MS-Indoor
Indoor
NO.1
Indoor
NO.2
Indoor
NO.3
Indoor
NO.4
MS-Indoor
Indoor
MS-Indoor
Indoor
NO.1
Indoor
NO.2
Indoor
NO.3
MS-MS
Upstream
MS
Downstream
MS
MS-MS
Upstream
MS
Downstream
MS
Downstream MS
Indoor
Unit NO.4
Indoor
Unit NO.3
Indoor
Unit NO.2
Indoor
Unit NO.1
(P Q E)
(P Q E)
(P Q E)
(P Q E)
(P Q E)
(P Q E)
(P Q E)
(P Q E)