V6R VRF 50/60Hz
135
Part 3
-
System Design and Installation
4 Refrigerant Piping Design
4.1 Design Considerations
Refrigerant piping design should take account of the following considerations:
The amount of brazing required should be kept to a minimum.
On the two inside sides of the first indoor branch joint (A in Figures 3-4.2, 3-4.3 and 3-4.4) the system should, as far
as possible, be equal in terms of number of units, total capacities and total piping lengths.
4.2 Material Specification
Only seamless phosphorus-deoxidized copper piping that complies with all applicable legislation should be used. Temper
grades and minimum thicknesses for different diameters of piping are specified in Table 3-4.1.
Table 3-4.1: Piping temper and thickness
Piping outer
diameter
(mm)
Temper
1
Minimum thickness
(mm)
Ф6.35
O
(annealed)
0.8
Ф9.53
0.8
Ф12.7
0.8
Ф15.9
1.0
Ф19.1
1.0
Ф22.2
1/2H
(half hard)
1.2
Ф25.4
1.2
Ф28.6
1.3
Ф31.8
1.5
Ф38.1
1.5
Ф41.3
1.5
Ф44.5
1.5
Ф54.0
1.8
Notes:
1. O: coiled piping; 1/2H: straight piping.

Other manuals for Midea V6R Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea V6R Series and is the answer not in the manual?

Midea V6R Series Specifications

General IconGeneral
BrandMidea
ModelV6R Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals