V6R VRF 50/60Hz
183
Part 3
-
System Design and Installation
V6R Series System Commissioning Report – Sheet D
Observed values
DSP1
content
Parameters displayed on DSP2
Remarks
Cooling
mode
Heating
mode
0.--
Unit address
Master unit: 0; slave units: 1, 2
1.--
Single module capacity
8-20HP
2.--
Number of outdoor units
Displayed on master unit PCB only
3.--
Number of indoor units as set on PCB
Displayed on master unit PCB only
4.--
Total capacity of outdoor unit
Only available for master unit, displayed
on slave units has no sense
5.--
Single module compressor frequency
Displayed on master unit PCB only
6.--
System compressor frequency
Actual value = value displayed × 10
7.--
System operating mode
0: off; 2: cooling; 3: heating; 4: main
heating; 5: main cooling.
8.--
Fan A speed index
Refer to Note 1
9.--
Fan B speed index
Refer to Note 1
10.--
Indoor heat exchanger pipe (T2) temperature (°C)
Actual value = value displayed
11.--
Indoor heat exchanger pipe (T2B) temperature (°C)
Actual value = value displayed
12.--
Main heat exchanger pipe (T3) temperature (°C)
Actual value = value displayed
13.--
Outdoor ambient (T4) temperature (°C)
Actual value = value displayed
14.--
Outdoor liquid pipe (T5) temperature (°C)
Actual value = value displayed
15.--
Plate heat exchanger cooling refrigerant inlet (T6A) temperature (°C)
Actual value = value displayed
16.--
Plate heat exchanger cooling refrigerant outlet (T6B) temperature
(°C)
Actual value = value displayed
17.--
Inverter compressor discharge (T7C1) temperature (°C)
Actual value = value displayed
18.--
Outdoor heat exchanger gas pipe (T8) temperature (°C)
Actual value = value displayed
19.--
Compressor inverter module internal (Ntc) temperature (°C)
Actual value = value displayed
20.--
Inverter module heatsink (T9)temperature (°C)
Actual value = value displayed
21.--
Outdoor heat exchanger liquid pipe (TL) temperature (°C)
Actual value = value displayed
22.--
Compressor suction (T7) temperature (°C)
Actual value = value displayed
23.--
Discharge superheat degree (°C)
Actual value = value displayed
24.--
Primary current (A)
Actual value = value displayed
25.--
EXVA position
Actual value = value displayed × 24
26.--
EXVC position
Actual value = value displayed × 4
27.--
Compressor discharge pressure (MPa)
Actual value = value displayed/10
28.--
Compressor suction pressure (MPa)
Actual value = value displayed/100
29.--
Number of indoor units currently in communication with master unit
Displayed on master unit PCB only
30.--
Number of indoor units currently operating
Displayed on master unit PCB only
31.--
Heat exchanger status
0-OFF; 1-Condenser; 2-Condenser (Not
used); 3-Evaporator; 4-Evaporator (Not
used)
32.--
System startup status
2~4-Startup control; 6-PI control;
33.--
Silent setting
Refer to Note 2
Table continued on next page
Project name and location
System name

Other manuals for Midea V6R Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea V6R Series and is the answer not in the manual?

Midea V6R Series Specifications

General IconGeneral
BrandMidea
ModelV6R Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals