V6R Series System Commissioning Report – Sheet D
Parameters displayed on DSP2
Master unit: 0; slave units: 1, 2
Displayed on master unit PCB only
Number of indoor units as set on PCB
Displayed on master unit PCB only
Total capacity of outdoor unit
Only available for master unit, displayed
on slave units has no sense
Single module compressor frequency
Displayed on master unit PCB only
System compressor frequency
Actual value = value displayed × 10
0: off; 2: cooling; 3: heating; 4: main
heating; 5: main cooling.
Indoor heat exchanger pipe (T2) temperature (°C)
Actual value = value displayed
Indoor heat exchanger pipe (T2B) temperature (°C)
Actual value = value displayed
Main heat exchanger pipe (T3) temperature (°C)
Actual value = value displayed
Outdoor ambient (T4) temperature (°C)
Actual value = value displayed
Outdoor liquid pipe (T5) temperature (°C)
Actual value = value displayed
Plate heat exchanger cooling refrigerant inlet (T6A) temperature (°C)
Actual value = value displayed
Plate heat exchanger cooling refrigerant outlet (T6B) temperature
(°C)
Actual value = value displayed
Inverter compressor discharge (T7C1) temperature (°C)
Actual value = value displayed
Outdoor heat exchanger gas pipe (T8) temperature (°C)
Actual value = value displayed
Compressor inverter module internal (Ntc) temperature (°C)
Actual value = value displayed
Inverter module heatsink (T9)temperature (°C)
Actual value = value displayed
Outdoor heat exchanger liquid pipe (TL) temperature (°C)
Actual value = value displayed
Compressor suction (T7) temperature (°C)
Actual value = value displayed
Discharge superheat degree (°C)
Actual value = value displayed
Actual value = value displayed
Actual value = value displayed × 24
Actual value = value displayed × 4
Compressor discharge pressure (MPa)
Actual value = value displayed/10
Compressor suction pressure (MPa)
Actual value = value displayed/100
Number of indoor units currently in communication with master unit
Displayed on master unit PCB only
Number of indoor units currently operating
Displayed on master unit PCB only
0-OFF; 1-Condenser; 2-Condenser (Not
used); 3-Evaporator; 4-Evaporator (Not
used)
2~4-Startup control; 6-PI control;
Table continued on next page …